Large motor step with high step PF

An 85 kW process load at 0.96 PF starts equipment that draws 180 kVA at 0.82 PF.

Inputs

Connected load
Site & fuel
A value of 1 uses the illustrative fuel curve. Use model-specific fuel data for final selection.

Load pickup and fuel consumption

60 Hz · US customaryEdit inputs
Load pickup and fuel consumption at 60 Hz STANDBY KW302.91kWSTANDBY KVA403.88kVASITE CAPACITY76.79%TANK RUNTIME33.45hModeled load stepSite limit 310.1 kVARunningPickupIllustrative fuel curveIdle → full load0%100% kWTank33.5 hSite rating76.8% retained100% rated

Detailed results
Required standby nameplate power
302.91 kW
Required standby nameplate capacity
403.88 kVA
Available capacity factor
76.79%
Elevation derating
21%
Temperature derating
2.8%
Pre-step running apparent power
88.54 kVA
Modeled pickup apparent power
268.54 kVA
Modeled pickup real power
232.6 kW
Available standby power at site
232.6 kW
Available standby capacity at site
310.13 kVA
Running load on nameplate
28.06%
Fuel rate at running load
8.61 gal/h
Fuel rate at 25% of nameplate
8 gal/h
Fuel rate at 50% of nameplate
12.99 gal/h
Fuel rate at 75% of nameplate
17.99 gal/h
Fuel rate at 100% of nameplate
23.32 gal/h
Usable diesel volume
288 gal
Estimated diesel runtime
33.45 h

Worked calculation

Check both 85/0.96 + 180 kVA and 85 + 180·0.82 kW. At 0.75 rated generator PF the real-power check governs the nameplate rating.

Modeled pickup real power
232.6 kW
Available standby power at site
232.6 kW
Required standby nameplate capacity
403.88 kVA

Values in this solution use the original example inputs.

Formulas & assumptions

Site derating

d = (1 − 0.035 · max(0, ft − 500)/1000) · (1 − 0.01 · max(0, °F − 77)/10)

Each factor applies continuously above its threshold. These are screening slopes, so use the engine and alternator manufacturer’s temperature and altitude ratings for selection.

Steady load and motor pickup

S_pickup = P_run/PF_run + S_step, P_pickup = P_run + S_step · PF_step

Treat running and step kVA as an arithmetic upper estimate. Divide by d. At the entered generator nameplate PF, size for whichever condition requires more kVA.

Fuel and sub-base tank

Runtime = tank volume · usable fraction / fuel rate at running load

Linearly interpolate the generic profile by fraction of standby nameplate kW. Diesel coefficients per rated kW are 0.010, 0.024, 0.039, 0.054 and 0.070 US gal/h at idle, 25%, 50%, 75% and 100%. Natural gas coefficients are 2.8, 4.4, 6.8, 9.3 and 12.0 scf/h at those points.

Screening model for standby service. Confirm site duty ratings, motor-start voltage and frequency excursions, and fuel curves with the equipment manufacturer. Pipeline gas has no sub-base tank runtime.