ASME B31.1 / B31.3 beam screen

Support span governed by bending

A header has a small remaining bending allowance after other loads are considered.

Inputs

Steel pipe section
Distributed loading
Spacing criteria
Maximum span
4.06m
Mid-span sag
1.083mm
Line mass
81.91kg/m
Stress used
151.9%
Span exceeds screening limit

Bending stress sets the shorter allowable span. Check both loads and the actual support arrangement.

Support spacing and sag

Support spacing and sagVertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.SPAN L5 mMID-SPAN δ1.083 mmUNLOADEDLOADEDPEAK SAG1.083 mmSAG LIMIT25 mmSPAN LIMIT4.06 m
Vertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.

All calculated values
Screened support span4.057 m
Governing criterionBending stress
Sag-limited span10.959 m
Stress-limited span4.057 m
Mid-span sag1.083 mm
Peak sag1.083 mm
Peak longitudinal bending stress9.113 MPa
Bending allowance used151.9 %
Outside diameter219.075 mm
Inside diameter202.717 mm
Nominal wall thickness8.179 mm
Second moment I3.02e+7 mm⁴
Section modulus Z275,451.786 mm³
Total distributed mass81.914 kg/m
Pipe mass per length42.538 kg/m
Fluid mass per length39.376 kg/m
Insulation mass per length0 kg/m

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Sum the distributed mass81.914 kg/m
  2. Calculate peak sag at trial spacing1.083 mm
  3. Use the shorter limit4.057 m

The tighter bending allowance sets the span even with a generous sag limit. Confirm combined longitudinal stresses separately.

Model and limits

The steel section uses nominal OD and wall dimensions. The distributed load includes the steel wall, full contents when selected, and the insulated annulus. The choice is between a simply supported span and two equal continuous spans carrying the same uniform load.

Default peak sag allowance is 0.10 in (2.54 mm). The sag peak for two equal spans is at about 42% of span from the outer support. The largest absolute bending moment is at the interior support. Include pressure, localized component loads, thermal loads, corrosion, support stiffness and combined sustained stress in the final B31.1 or B31.3 review.

View equations and references