ASME B31.1 / B31.3 beam screen
Heavy liquid in a Schedule 80 line
A dense process liquid flows in an insulated DN 50 line with a substantial trial support spacing.
Inputs
Results
Edit inputs- Maximum span
- 3.33m
- Mid-span sag
- 10.902mm
- Line mass
- 11.62kg/m
- Stress used
- 33.1%
Peak sag sets the shorter allowable span. Check both loads and the actual support arrangement.
Support spacing and sag
All calculated values
| Screened support span | 3.335 m |
|---|---|
| Governing criterion | Peak sag |
| Sag-limited span | 3.335 m |
| Stress-limited span | 8.341 m |
| Mid-span sag | 10.902 mm |
| Peak sag | 10.902 mm |
| Peak longitudinal bending stress | 27.402 MPa |
| Bending allowance used | 33.1 % |
| Outside diameter | 60.325 mm |
| Inside diameter | 49.251 mm |
| Nominal wall thickness | 5.537 mm |
| Second moment I | 361,256.138 mm⁴ |
| Section modulus Z | 11,976.996 mm³ |
| Total distributed mass | 11.62 kg/m |
| Pipe mass per length | 7.482 kg/m |
| Fluid mass per length | 2.896 kg/m |
| Insulation mass per length | 1.243 kg/m |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Sum the distributed mass11.62 kg/m
- Calculate peak sag at trial spacing10.902 mm
- Use the shorter limit3.335 m
A thicker wall adds stiffness and weight. Compare peak sag at the installed spacing with the project drainage limit.
Model and limits
The steel section uses nominal OD and wall dimensions. The distributed load includes the steel wall, full contents when selected, and the insulated annulus. The choice is between a simply supported span and two equal continuous spans carrying the same uniform load.
Default peak sag allowance is 0.10 in (2.54 mm). The sag peak for two equal spans is at about 42% of span from the outer support. The largest absolute bending moment is at the interior support. Include pressure, localized component loads, thermal loads, corrosion, support stiffness and combined sustained stress in the final B31.1 or B31.3 review.
View equations and references