ASME B31.1 / B31.3 beam screen

Two equal continuous pipe spans

A uniform six-inch header passes over a middle support and continues across an equal neighboring span.

Inputs

Steel pipe section
Distributed loading
Spacing criteria
Maximum span
22.55ft
Mid-span sag
0.039in
Line mass
33.75lb/ft
Stress used
16.1%
Span within screening limit

Peak sag governs the calculated span. Full longitudinal stress and support loads need a separate check.

Support spacing and sag

Support spacing and sagVertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.SPAN L18 ftMID-SPAN δ0.039 inUNLOADEDLOADEDPEAK SAG0.041 inSAG LIMIT0.1 inSPAN LIMIT22.55 ft
Vertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.

All calculated values
Screened support span22.547 ft
Governing criterionPeak sag
Sag-limited span22.547 ft
Stress-limited span44.876 ft
Mid-span sag0.039 in
Peak sag0.041 in
Peak longitudinal bending stress1.931 ksi
Bending allowance used16.1 %
Outside diameter6.625 in
Inside diameter6.065 in
Nominal wall thickness0.28 in
Second moment I28.142 in⁴
Section modulus Z8.496 in³
Total distributed mass33.75 lb/ft
Pipe mass per length18.994 lb/ft
Fluid mass per length12.5 lb/ft
Insulation mass per length2.255 lb/ft

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Sum the distributed mass33.75 lb/ft
  2. Calculate peak sag at trial spacing0.041 in
  3. Use the shorter limit22.547 ft

Peak sag is slightly away from center, so the maximum-span calculation uses peak deflection. The interior support still sees bending.

Model and limits

The steel section uses nominal OD and wall dimensions. The distributed load includes the steel wall, full contents when selected, and the insulated annulus. The choice is between a simply supported span and two equal continuous spans carrying the same uniform load.

Default peak sag allowance is 0.10 in (2.54 mm). The sag peak for two equal spans is at about 42% of span from the outer support. The largest absolute bending moment is at the interior support. Include pressure, localized component loads, thermal loads, corrosion, support stiffness and combined sustained stress in the final B31.1 or B31.3 review.

View equations and references

Worked examples