ASME B31.1 / B31.3 beam screen

Drainable process line with a tight sag limit

A clean process drain has a stringent drainage pocket allowance across adjacent equal spans.

Inputs

Steel pipe section
Distributed loading
Spacing criteria
Maximum span
3.41m
Mid-span sag
0.86mm
Line mass
5.36kg/m
Stress used
13.4%
Span within screening limit

Peak sag governs the calculated span. Full longitudinal stress and support loads need a separate check.

Support spacing and sag

Support spacing and sagVertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.SPAN L3 mMID-SPAN δ0.86 mmUNLOADEDLOADEDPEAK SAG0.894 mmSAG LIMIT1.5 mmSPAN LIMIT3.41 m
Vertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.

All calculated values
Screened support span3.415 m
Governing criterionPeak sag
Sag-limited span3.415 m
Stress-limited span8.205 m
Mid-span sag0.86 mm
Peak sag0.894 mm
Peak longitudinal bending stress11.062 MPa
Bending allowance used13.4 %
Outside diameter48.26 mm
Inside diameter40.894 mm
Nominal wall thickness3.683 mm
Second moment I128,987.802 mm⁴
Section modulus Z5,345.537 mm³
Total distributed mass5.36 kg/m
Pipe mass per length4.049 kg/m
Fluid mass per length1.311 kg/m
Insulation mass per length0 kg/m

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Sum the distributed mass5.36 kg/m
  2. Calculate peak sag at trial spacing0.894 mm
  3. Use the shorter limit3.415 m

The support spacing follows peak sag. The check assumes equal level supports and uniform load, so survey actual slopes.

Model and limits

The steel section uses nominal OD and wall dimensions. The distributed load includes the steel wall, full contents when selected, and the insulated annulus. The choice is between a simply supported span and two equal continuous spans carrying the same uniform load.

Default peak sag allowance is 0.10 in (2.54 mm). The sag peak for two equal spans is at about 42% of span from the outer support. The largest absolute bending moment is at the interior support. Include pressure, localized component loads, thermal loads, corrosion, support stiffness and combined sustained stress in the final B31.1 or B31.3 review.

View equations and references