ASME B31.1 / B31.3 beam screen
Drainable process line with a tight sag limit
A clean process drain has a stringent drainage pocket allowance across adjacent equal spans.
Inputs
Results
Edit inputs- Maximum span
- 3.41m
- Mid-span sag
- 0.86mm
- Line mass
- 5.36kg/m
- Stress used
- 13.4%
Peak sag governs the calculated span. Full longitudinal stress and support loads need a separate check.
Support spacing and sag
All calculated values
| Screened support span | 3.415 m |
|---|---|
| Governing criterion | Peak sag |
| Sag-limited span | 3.415 m |
| Stress-limited span | 8.205 m |
| Mid-span sag | 0.86 mm |
| Peak sag | 0.894 mm |
| Peak longitudinal bending stress | 11.062 MPa |
| Bending allowance used | 13.4 % |
| Outside diameter | 48.26 mm |
| Inside diameter | 40.894 mm |
| Nominal wall thickness | 3.683 mm |
| Second moment I | 128,987.802 mm⁴ |
| Section modulus Z | 5,345.537 mm³ |
| Total distributed mass | 5.36 kg/m |
| Pipe mass per length | 4.049 kg/m |
| Fluid mass per length | 1.311 kg/m |
| Insulation mass per length | 0 kg/m |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Sum the distributed mass5.36 kg/m
- Calculate peak sag at trial spacing0.894 mm
- Use the shorter limit3.415 m
The support spacing follows peak sag. The check assumes equal level supports and uniform load, so survey actual slopes.
Model and limits
The steel section uses nominal OD and wall dimensions. The distributed load includes the steel wall, full contents when selected, and the insulated annulus. The choice is between a simply supported span and two equal continuous spans carrying the same uniform load.
Default peak sag allowance is 0.10 in (2.54 mm). The sag peak for two equal spans is at about 42% of span from the outer support. The largest absolute bending moment is at the interior support. Include pressure, localized component loads, thermal loads, corrosion, support stiffness and combined sustained stress in the final B31.1 or B31.3 review.
View equations and references