ASME B31.1 / B31.3 beam screen

Empty Schedule 10 process line

An empty welded steel line is checked at its temporary erection support spacing.

Inputs

Steel pipe section
Distributed loading
Spacing criteria
Maximum span
15.26ft
Mid-span sag
0.038in
Line mass
4.34lb/ft
Stress used
7.5%
Span within screening limit

Peak sag governs the calculated span. Full longitudinal stress and support loads need a separate check.

Support spacing and sag

Support spacing and sagVertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.SPAN L12 ftMID-SPAN δ0.038 inUNLOADEDLOADEDPEAK SAG0.038 inSAG LIMIT0.1 inSPAN LIMIT15.26 ft
Vertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.

All calculated values
Screened support span15.256 ft
Governing criterionPeak sag
Sag-limited span15.256 ft
Stress-limited span43.826 ft
Mid-span sag0.038 in
Peak sag0.038 in
Peak longitudinal bending stress0.9 ksi
Bending allowance used7.5 %
Outside diameter3.5 in
Inside diameter3.26 in
Nominal wall thickness0.12 in
Second moment I1.822 in⁴
Section modulus Z1.041 in³
Total distributed mass4.336 lb/ft
Pipe mass per length4.336 lb/ft
Fluid mass per length0 lb/ft
Insulation mass per length0 lb/ft

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Sum the distributed mass4.336 lb/ft
  2. Calculate peak sag at trial spacing0.038 in
  3. Use the shorter limit15.256 ft

Empty weight reduces bending and sag. Recheck the hydrotest or operating fill case before setting permanent supports.

Model and limits

The steel section uses nominal OD and wall dimensions. The distributed load includes the steel wall, full contents when selected, and the insulated annulus. The choice is between a simply supported span and two equal continuous spans carrying the same uniform load.

Default peak sag allowance is 0.10 in (2.54 mm). The sag peak for two equal spans is at about 42% of span from the outer support. The largest absolute bending moment is at the interior support. Include pressure, localized component loads, thermal loads, corrosion, support stiffness and combined sustained stress in the final B31.1 or B31.3 review.

View equations and references

Worked examples