ASME B31.1 / B31.3 beam screen
Empty Schedule 10 process line
An empty welded steel line is checked at its temporary erection support spacing.
Inputs
Results
Edit inputs- Maximum span
- 15.26ft
- Mid-span sag
- 0.038in
- Line mass
- 4.34lb/ft
- Stress used
- 7.5%
Peak sag governs the calculated span. Full longitudinal stress and support loads need a separate check.
Support spacing and sag
All calculated values
| Screened support span | 15.256 ft |
|---|---|
| Governing criterion | Peak sag |
| Sag-limited span | 15.256 ft |
| Stress-limited span | 43.826 ft |
| Mid-span sag | 0.038 in |
| Peak sag | 0.038 in |
| Peak longitudinal bending stress | 0.9 ksi |
| Bending allowance used | 7.5 % |
| Outside diameter | 3.5 in |
| Inside diameter | 3.26 in |
| Nominal wall thickness | 0.12 in |
| Second moment I | 1.822 in⁴ |
| Section modulus Z | 1.041 in³ |
| Total distributed mass | 4.336 lb/ft |
| Pipe mass per length | 4.336 lb/ft |
| Fluid mass per length | 0 lb/ft |
| Insulation mass per length | 0 lb/ft |
Worked solution
These steps show the starting preset. The calculator above follows your edits.
- Sum the distributed mass4.336 lb/ft
- Calculate peak sag at trial spacing0.038 in
- Use the shorter limit15.256 ft
Empty weight reduces bending and sag. Recheck the hydrotest or operating fill case before setting permanent supports.
Model and limits
The steel section uses nominal OD and wall dimensions. The distributed load includes the steel wall, full contents when selected, and the insulated annulus. The choice is between a simply supported span and two equal continuous spans carrying the same uniform load.
Default peak sag allowance is 0.10 in (2.54 mm). The sag peak for two equal spans is at about 42% of span from the outer support. The largest absolute bending moment is at the interior support. Include pressure, localized component loads, thermal loads, corrosion, support stiffness and combined sustained stress in the final B31.1 or B31.3 review.
View equations and references