ASME B31.1 / B31.3 beam screen

Heavy liquid in a Schedule 80 line

A dense process liquid flows in an insulated DN 50 line with a substantial trial support spacing.

Inputs

Steel pipe section
Distributed loading
Spacing criteria
Maximum span
3.33m
Mid-span sag
10.902mm
Line mass
11.62kg/m
Stress used
33.1%
Span exceeds screening limit

Peak sag sets the shorter allowable span. Check both loads and the actual support arrangement.

Support spacing and sag

Support spacing and sagVertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.SPAN L4.8 mMID-SPAN δ10.902 mmUNLOADEDLOADEDPEAK SAG10.902 mmSAG LIMIT2.54 mmSPAN LIMIT3.33 m
Vertical movement is exaggerated. The marker shows peak sag, which shifts away from mid-span for two equal continuous spans.

All calculated values
Screened support span3.335 m
Governing criterionPeak sag
Sag-limited span3.335 m
Stress-limited span8.341 m
Mid-span sag10.902 mm
Peak sag10.902 mm
Peak longitudinal bending stress27.402 MPa
Bending allowance used33.1 %
Outside diameter60.325 mm
Inside diameter49.251 mm
Nominal wall thickness5.537 mm
Second moment I361,256.138 mm⁴
Section modulus Z11,976.996 mm³
Total distributed mass11.62 kg/m
Pipe mass per length7.482 kg/m
Fluid mass per length2.896 kg/m
Insulation mass per length1.243 kg/m

Worked solution

These steps show the starting preset. The calculator above follows your edits.

  1. Sum the distributed mass11.62 kg/m
  2. Calculate peak sag at trial spacing10.902 mm
  3. Use the shorter limit3.335 m

A thicker wall adds stiffness and weight. Compare peak sag at the installed spacing with the project drainage limit.

Model and limits

The steel section uses nominal OD and wall dimensions. The distributed load includes the steel wall, full contents when selected, and the insulated annulus. The choice is between a simply supported span and two equal continuous spans carrying the same uniform load.

Default peak sag allowance is 0.10 in (2.54 mm). The sag peak for two equal spans is at about 42% of span from the outer support. The largest absolute bending moment is at the interior support. Include pressure, localized component loads, thermal loads, corrosion, support stiffness and combined sustained stress in the final B31.1 or B31.3 review.

View equations and references