Available embedmentAvailable length ≥ required length for the selected detail
Outside limit
High-grade bar confinementKtr ≥ 0.5db for fy ≥ 80 ksi and spacing < 6 in
Outside limit
Ordinary nonseismic tension details. Available length is measured along the straight bar or to the outside of the hook. Check minimum cover, bend fabrication and confinement at discontinuous ends separately.
Use cᵦ = min(clear cover + db/2, bar spacing/2). Cap (cᵦ + Ktr)/db at 2.5, ψtψe at 1.7 and √f′c at 100. Calculate ℓd from Eq. (25.4.2.4a) with a 12 in floor.
Check a Class B splice with the §25.5.2 minimum: multiply the unfloored ℓd by 1.3 and then apply the 12 in floor. The detail readout also shows 1.3 times the floored straight length for comparison.
Use Eq. (25.4.3.1) and its own hook factors for ℓdh, subject to 8db and 6 in minima. A 90° hook needs a 12db tail; a 180° hook needs max(4db, 2.5 in). Check the outer bend envelope and tail run.
Deformed tension bars · standard hooks · Limit exceeded
Inputs
Bar size
#8
Concrete strength f′c
4,000 psi
Steel grade fy
80 ksi
Concrete weight
Normalweight (λ = 1.00)
Top-cast bar
Yes
Epoxy coated
Yes
Minimum clear cover
1.5 in
Bar spacing c/c
5 in
Confinement index Ktr
0 in
Detail to screen
Straight bar
Available length
48 in
Hook inside column core
No
Hook confinement Ath/Ahs
0
Calculated values
Straight development ℓd
92.73 in
Hook development ℓdh
47.84 in
Class B with 1.3 × floored ℓd
120.55 in
Confinement (cᵦ + Ktr)/db
2
Nominal bar diameter db
1 in
Spacing/cover term cᵦ
2 in
Selected required length
92.73 in
Class B minimum per §25.5.2
120.55 in
Minimum inside bend diameter
6 in
90° straight tail
12 in
180° straight tail
4 in
Top cast ψt
1.3
Epoxy ψe (straight)
1.5
Size ψs
1
Grade ψg
1.15
Hook confinement ψr
1.6
Hook location ψo
1.25
Hook concrete ψc
0.867
Screening
Straight tension bar · Required / available length 193.2%
Available embedment · Outside limit
High-grade bar confinement · Outside limit
Ordinary nonseismic tension details. Available length is measured along the straight bar or to the outside of the hook. Check minimum cover, bend fabrication and confinement at discontinuous ends separately.