Available embedmentAvailable length ≥ required length for the selected detail
Within limit
Hook tail runTail ≥ 12db
Within limit
Bend envelopeClear envelope ≥ minimum inside bend diameter + 2db
Within limit
Ordinary nonseismic tension details. Available length is measured along the straight bar or to the outside of the hook. Check minimum cover, bend fabrication and confinement at discontinuous ends separately.
Use cᵦ = min(clear cover + db/2, bar spacing/2). Cap (cᵦ + Ktr)/db at 2.5, ψtψe at 1.7 and √f′c at 100. Calculate ℓd from Eq. (25.4.2.4a) with a 12 in floor.
Check a Class B splice with the §25.5.2 minimum: multiply the unfloored ℓd by 1.3 and then apply the 12 in floor. The detail readout also shows 1.3 times the floored straight length for comparison.
Use Eq. (25.4.3.1) and its own hook factors for ℓdh, subject to 8db and 6 in minima. A 90° hook needs a 12db tail; a 180° hook needs max(4db, 2.5 in). Check the outer bend envelope and tail run.
Deformed tension bars · standard hooks · Within screening limits
Inputs
Bar size
#6
Concrete strength f′c
4,000 psi
Steel grade fy
60 ksi
Concrete weight
Normalweight (λ = 1.00)
Top-cast bar
No
Epoxy coated
No
Minimum clear cover
3 in
Bar spacing c/c
6 in
Confinement index Ktr
0 in
Detail to screen
90° standard hook
Available length
16 in
Hook inside column core
Yes
Hook confinement Ath/Ahs
0
Clear hook tail run
10 in
Clear bend envelope
7 in
Calculated values
Straight development ℓd
17.08 in
Hook development ℓdh
9.71 in
Class B with 1.3 × floored ℓd
22.2 in
Confinement (cᵦ + Ktr)/db
2.5
Nominal bar diameter db
0.75 in
Spacing/cover term cᵦ
3 in
Selected required length
9.71 in
Class B minimum per §25.5.2
22.2 in
Minimum inside bend diameter
4.5 in
90° straight tail
9 in
180° straight tail
3 in
Top cast ψt
1
Epoxy ψe (straight)
1
Size ψs
0.8
Grade ψg
1
Hook confinement ψr
1
Hook location ψo
1
Hook concrete ψc
0.867
Screening
90° standard hook · Required / available length 60.7%
Available embedment · Within limit
Hook tail run · Within limit
Bend envelope · Within limit
Ordinary nonseismic tension details. Available length is measured along the straight bar or to the outside of the hook. Check minimum cover, bend fabrication and confinement at discontinuous ends separately.