RoomAcousticLab · Calculation record
Indoor sound field example
Lecture room ceiling replacement
A partial replacement adds absorption without changing the source or receiver location. Compare the prediction at the listener with the diffuse-only change.
Inputs
- Sound level
- 73.3dB
- Critical dist.
- 1.38m
- Direct share
- 2.9%
- Level drop
- 1.96dB
Direct and reflected energy paths
Illustrative scaleSmall receiver reserve
ReviewThere is less than 3 dB of modelled reserve against the entered target.
≥ 3 dB reserveReviewOver target
Input snapshot
- Total surface area
- 470 m²
- Mean absorption α
- 0.17
- Sound power Lw
- 87 dB
- Directivity Q
- 1 · Full space
- Receiver distance
- 8 m
- Receiver target
- 74 dB
- Treatment option
- Replace ceiling finish
- Ceiling area treated
- 60 m²
- Existing ceiling α
- 0.12
- New ceiling α
- 0.72
Calculation breakdown
- Room constant R
- 96.27 m²
- Direct level
- 57.95 dB
- Reverberant level
- 73.19 dB
- Receiver regime
- Reverberant dominated
- Treated mean absorption α
- 0.2466
- Treated receiver level
- 71.35 dB
- Diffuse-only level drop
- 2.04 dB
At ᾱ = 1, R diverges and the diffuse term vanishes. At ᾱ = 0, the ideal enclosure has no finite steady-state reverberant level. The model omits discrete room modes and early-reflection interference.