RoomAcousticLab · Calculation record
Reverberation time example
Restaurant panel substitution
A proposed finish absorbs less than the existing ceiling in the selected band. Check what happens when the replacement cannot add absorption.
Inputs
Use absorption coefficients for the same frequency band.
- Sabine
- 0.998s
- Eyring
- 0.913s
- Fitzroy
- 1.05s
- Panel area
- —
Room section & absorption
Illustrative scaleTreatment cannot lower RT60
LimitThe panel coefficient must exceed the baseline coefficient of the selected surface.
Target metPanels neededInfeasible
Input snapshot
- Length
- 13 m
- Width
- 8 m
- Height
- 3.5 m
- End walls αx
- 0.09
- Side walls αy
- 0.11
- Floor / ceiling αz
- 0.21
- Air temperature
- 20 °C
- Target RT60
- 0.5 s
- Size panels with
- Eyring
- Treatment surface
- Floor / ceiling · z
- Panel absorption α
- 0.18
- Available area
- 60 m²
Calculation breakdown
- Room volume
- 364 m³
- Room surface area
- 355 m²
- Equivalent absorption area
- 58.73 m²
- Mean absorption α
- 0.1654
- Treatment sizing model
- Eyring
- Baseline α of selected pair
- 0.21
- Selected pair area
- 208 m²
- Decay before treatment
- 0.913 s
- Decay with proposed area
- No feasible area
- Best decay within allowance
- 0.913 s
Use Sabine in the low-absorption regime, Eyring for a more evenly distributed field, and Fitzroy when opposite pairs differ. The models omit air absorption, leakage and non-diffuse geometry. Measured decay and installed band coefficients should drive a final specification.