RoomAcousticLab · Calculation record
Outdoor noise setback example
Roof fan at the property line
Use a half-space screening assumption for one rooftop fan. Estimate the property-line level at 28 metres and solve the distance to the entered limit.
Inputs
- Receiver SPL
- 60dB
- Setback
- 39.5m
- Air loss
- 0.06dB
- Limit margin
- -3.02dB
Source geometry & receiver setback
Illustrative scaleProperty-line limit exceeded
LimitThe modelled value falls on the wrong side of the entered target.
≥ 3 dB reserve0–3 dB reserveOver limit
Input snapshot
- Source type
- Point source
- Sound power Lw
- 97 dB
- Directivity Q
- 2 · Half space
- Identical sources
- 1
- Source addition
- Incoherent · energy
- Receiver distance
- 28 m
- Air attenuation
- 2 dB/km
- Property-line limit
- 57 dB
Calculation breakdown
- Geometrical spreading loss
- 39.94 dB
- Directivity gain
- 3.01 dB
- Identical-source addition
- 0 dB
- Entered property-line limit
- 57 dB
- Setback search result
- Solved inside model range
Setback is solved between 0.1 m and 100 km. This model considers divergence and the entered air loss. A site study can include ground impedance, shielding, weather, reflections, background and source spectra as required by the governing method.