Single-Pane to Low-E Windows in a Winter Climate

Eight existing single-pane windows average 18 ft² each and have a whole-window U-factor of 1.02. An upgrade quote proposes U-0.32 low-E windows for a 72°F design temperature difference.

Try it Compare a U-0.27 option beside the U-0.32 quote. Enter its incremental price so the extra energy savings are compared with the extra cost.

Window assembly
ft²
Btu/(h·ft²·°F)
Btu/(h·ft²·°F)
Climate and costs
°F·days

Use a consistent base, typically 65°F (18.3°C).

°F
$/MMBtu

Enter the price per unit of fuel input energy.

%
USD
Peak heat-loss reduction
7,258 Btu/h
Estimated energy savings / year
369.48 USD
Simple payback
13 years

Savings reflect changes in conductive heat loss at the same window area.

Conductive window heat loss

Existing and proposed window heat lossExisting 10,575 Btu/h. Proposed 3,318 Btu/h. 05K10K15K20KExisting windows10,575 Btu/hU 1.02 Btu/(h·ft²·°F)Proposed windows3,318 Btu/hU 0.32 Btu/(h·ft²·°F)Peak conductive heat loss · Btu/h
The chart compares peak conductive heat loss for the existing and proposed window assemblies at the same temperature difference.
Total window area
144 ft²
Existing peak loss
10,575 Btu/h
Proposed peak loss
3,318 Btu/h
Delivered heat saved / year
15.483 MMBtu
Fuel input saved / year
17.594 MMBtu
Download

How this calculation works

Multiply count by average whole-window area. Conductive design heat loss equals U × area × the design indoor–outdoor temperature difference.

Annual delivered heat savings are the old-to-new difference in UA multiplied by heating degree days and 24 hours per day. Divide by seasonal efficiency to get fuel input saved, then multiply by your marginal energy price.

Simple payback divides incremental installed cost by positive annual dollar savings. This comparison covers conduction only. Solar gain, air leakage, cooling, maintenance and comfort may also affect the project decision.

References

Frequently asked questions

How does the low-E replacement reduce winter peak heat loss by over 7,000 Btu/h?

The U-factor drops by 0.70 across 144 ft². Multiplying that change by the 72°F design difference gives 7,257.6 Btu/h less conductive loss.

Should I include new window opening sizes in the winter upgrade run?

If sizes change, calculate old and new conductive losses separately with their respective areas. This calculator holds area constant for the comparison.