WaterTreatLab

Calculation Methodology & Engineering References

See the conversion conventions, model assumptions and EPA, AWWA, WEF and manufacturer references behind the WaterTreatLab equations.

Calculation and units

Use a consistent process boundary and operating point. Concentrations stay in their chemical reporting basis as units switch. US volumes use the US gallon. The model converts physical quantities with 1 gal = 3.785411784 L, 1 ft = 0.3048 m and 1 lb = 0.45359237 kg.

Operator mass loading uses 8.34 lb/day per MGD·mg/L. Metric readouts convert the same result to kg/day. The displayed values are rounded, and exports retain the calculated numerical values.

Process equations and sources

Reverse osmosis
The 75% system-recovery screen and 18/14/12 GFD well/surface/reuse screens are preliminary review triggers. DuPont Table 22 varies by pretreatment and feed SDI and lists separate element-level limits. AWWA M46 and the selected membrane projection provide design context.
Chemical metering
The 10% and 90% marks flag turndown and capacity margin for review. The pump’s calibrated performance curve governs the actual setting. Dose and residual have distinct meanings in treatment.
Ion-exchange softening
The 1–5 gpm/ft³ service range is a C100 bulletin reference. Capacity can change with water chemistry, bed depth, flow and resin condition. Combined Fe/Mn above 0.5 mg/L calls for pretreatment and resin review under conventional waterworks guidance.
Chlorine contact time
A CT ratio at or above one means the calculated value meets your entered target for this segment. A regulated inactivation determination also requires the governing method, sampling, operating envelope and any segment accounting.
Clarifier hydraulics
Ten States §4.2.5 gives 4 h conventional water sedimentation, an authority-approved reduced-time pathway at 0.5 gpm/ft² or demonstrated equivalent settling, and 20,000 gpd/ft outlet loading. EPA primary wastewater reference bands are 600–1,200 gpd/ft², 1–4 h and 10,000–20,000 gpd/ft. AWWA M37 covers water clarification design context.
Activated sludge
WEF 11 and EPA process-control guidance place F/M and MCRT in the context of plant operations. SVI below 70 or above 150 mL/g prompts review for atypical settling. Confirm actual settling, clarity and oxygen demand with samples and site data.
UV disinfection
The optical estimate assumes uniform axial flow and independent lamp contributions. Short circuiting, lamp arrangement, sensor response and the dose distribution require manufacturer validation. EPA RED comes from biodosimetry.
Granular filter backwash
The EPA water-wash expansion reference is commonly 20–25% and varies with media and air scour. Verify the bed with a rise measurement or media supplier curve and check trough clearance. The model assumes discrete water and air volumes.

Questions

Does switching units change calculation precision?

The original numerical state stays in one calculation basis. Changing the display converts that state once per display, so toggling back recovers the original values.

Which engineering factors are approximate?

The 8.34 load factor is an operator convention. RO osmotic pressure, UV optics, carbon oxygen demand and filter expansion use stated screening assumptions.

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.