WaterTreatLab

Granular filtration

Filter Backwash Rise Rate, Bed Expansion & Air Scour

Estimate rapid sand or dual-media filter wash flow, washwater use, temperature adjustment, bed expansion and air scour volume.

Inputs

Filter cell
ft²
ft
ft
Zero uses the estimate
gal/d
Water backwash
gpm/ft²
°F
min
d⁻¹
Air scour
scfm/ft²
min

Results

US customary
Backwash pump flow
2,550 gpm
Water per wash
20,400 gal
Bed expansion
22.5 %
Daily UBRW
2.72 %
Filter bed fluidizationLive diagram
Filter bed fluidizationSettled and expanded bed profiles across the filter cell. Settled bed2.5 ftDuring wash3.0625 ftWater flow2,550 gpmExpansion22.5 %Air volume2,400 scf
Settled and expanded bed profiles across the filter cell.
Actual wash rise rate
17 gpm/ft² 41.561 m/h
Equivalent rise rate at 20 °C
17 gpm/ft² 41.561 m/h
Expanded depth
3.0625 ft
Daily washwater
20,400 gal/d
Air scour flow
600 scfm
Air volume per scour
2,400 scf
Water viscosity
1.0017 mPa·s

For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.

Worked examples

Equations & conventions

Rise rate and washwater
Qwash = A × v, Vwash = Qwash × t

The result is gpm with area in ft² and rise rate in gpm/ft². UBRW is 100 × daily washwater / gross daily production for the same cell.

Temperature adjustment
μ = 0.02414 × 10^(247.8/(Tc + 133.15)), vT = v₂₀ × (μ₂₀/μT)^0.35

μ is an approximate water viscosity in mPa·s. Select whether the input is already at wash temperature or is the reference at 20 °C. The exponent is a planning assumption chosen to approximate seasonal behavior.

Measured bed expansion
Expansion = 100 × (expanded depth / settled depth − 1)

Enter the total operating bed depth during wash. The settled and expanded depths exclude support gravel.

Modeled bed expansion
ε = min(0.80, εref × (v₂₀/vref)^(1/3)); E = 100 × max(0, (1−ε₀)/(1−ε) − 1)

The porosity screen uses ε₀ = 0.40 and εref = 1 − (1 − ε₀)/1.225. The illustrative 20 °C reference rates are 15/17/19 gpm/ft² for sand/dual/anthracite. Use measured depth or a media-specific curve for plant decisions.

Air scour
Air volume = specific standard airflow × A × air time

Report gas volume at the same standard conditions as the entered rate. The 3–5 scfm/ft² Ten States reference applies to underdrain introduction.

Planning basis

The EPA water-wash expansion reference is commonly 20–25% and varies with media and air scour. Verify the bed with a rise measurement or media supplier curve and check trough clearance. The model assumes discrete water and air volumes.

Questions

Why does a colder backwash use a lower rate at equal expansion?

Cold water has higher viscosity and exerts more drag at the same velocity. Use media-specific temperature data or site tests for the adjustment.

What production volume should I use for UBRW?

Enter gross daily filtered water from the same cell whose wash volume and wash frequency you entered. Use an aligned period and production boundary.