Hypochlorite Feed at 2 MGD
Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.
Chemical feed
Convert an active mg/L target to lb/day, gph and mL/min. Estimate metering pump capacity, day-tank autonomy and bulk inventory.
For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.
Calculate active chemical pounds per day, metering pump flow and day-tank autonomy for a 2 MGD hypochlorite case.
Size pump flow for a 0.5% active polymer solution delivering a 0.8 mg/L active dose to 0.75 MGD.
Check liquid coagulant feed at 6 MGD, with a 25 mg/L active target and a 9.5 gph rated metering pump.
Find why a 1 gph pump is oversized for a 0.01236 gph feed target on a small industrial water stream.
Compare a requested 8 mg/L active dose with what an 8 gph pump can meet at peak process flow.
Model a chemical system in standby at zero target dose while the treatment process continues to flow.
Work out phosphate metering flow, capacity and days of usable stock for a 1.8 MGD process.
W = 8.34 × Qₘɢᴅ × DQ is US million gallons per day, D is mg/L of active chemical and W is lb/day. The tool uses the EPA operator convention of 8.34 exactly.
q = W / (24 × 8.34 × SG × w)w is active mass fraction, for example 0.125 at 12.5% w/w. The result is US gal/h. Use the stock-specific SG and the same active chemical basis as the dose target.
Setting = 100q / qᵣₐₜₑ𝒹, autonomy = Vᵤₛₐᵦₗₑ / (24q)Pump setting is the equivalent share of rated flow. Calibrate stroke and speed at actual pressure. Use liquid inventory above the unusable heel and any reserved stock.
The 10% and 90% marks flag turndown and capacity margin for review. The pump’s calibrated performance curve governs the actual setting. Dose and residual have distinct meanings in treatment.
Percent by mass is active chemical mass divided by total solution mass. Ask the supplier for active w/w strength if the label reports trade percent, volume strength or a different chemical basis.
Use the manufacturer rating at the actual discharge pressure or the measured maximum at that pressure. A catalog rating at another pressure can misstate the available capacity.
WaterTreatLab / Current operating point
US customary units