WeibullMTBFLab · Engineering calculation
Hyperscale PSU recovery SLA budget
Model a monitored rack power service with 80,000 hours of mean uptime and four hours of total downtime per incident.
Operational availability meets SLA
Inputs
- Mean uptime MTBF
- 80,000 h
- Corrective repair MTTR
- 0.5 h
- Additional downtime MDT
- 3.5 h
- SLA target
- 99.99 %
- Mission time
- 24 h
Results
- Inherent Aᵢ
- 99.999375 %
- Operational Aₒ
- 99.99500025 %
- Downtime/yr
- 0.4379781 h/yr
- Transient A(t)
- 99.999375 %
- Annual downtime
- 26.27869 min/yr
- Annual SLA budget
- 0.876 h/yr
- SLA headroom
- 0.4380219 h/yr
- Operational SLA tier
- 4 nines
Aᵢ = MTBF / (MTBF + MTTR)Corrective repair alone gives 99.999375%.Aₒ = MTBF / (MTBF + MTTR + MDT)Additional downtime brings operational availability to 99.99500025%.Downtime/yr = 8,760 (1 − Aₒ)Annual downtime is 0.4379781 hours or 26.27869 minutes.A(t) = Aᵢ + (1−Aᵢ) exp[−(1/MTBF + 1/MTTR)t]Starting fully up, transient availability at 24 h is 99.999375%.
MTBF is mean uptime, excluding downtime. Enter only additional preventive and logistics downtime per uptime cycle in MDT. The two-state Markov model uses exponential up and repair durations.