Hyperscale infrastructure case

Hyperscale PSU recovery SLA budget

Model a monitored rack power service with 80,000 hours of mean uptime and four hours of total downtime per incident.

Inputs

h
h
h
%
h
PassOperational availability meets SLA
Inherent Aᵢ
99.9994%
Operational Aₒ
99.995%
Downtime/yr
0.437978h/yr
Transient A(t)
99.9994%

Markov states and downtime budget

Two-state Markov transition, downtime budget and transient unavailabilityTwo-state repair modelUpDownFailure λRepair μAnnual downtime budget0.438 h actual0.876 h SLAMarkov transient · 1 − A(t)0%3.5e-4%7.1e-4%09.218.427.6Time (h)TransientSteady state

The transient curve starts fully up and uses active corrective repair. The SLA comparison uses operational downtime.

Download

Detailed results

Annual downtime
26.27869 min/yr
Annual SLA budget
0.876 h/yr
SLA headroom
0.4380219 h/yr
Operational SLA tier
4 nines

Translate the operational downtime fraction into annual minutes and compare with the 99.99% target budget.

Formula trace

  1. Aᵢ = MTBF / (MTBF + MTTR)Corrective repair alone gives 99.999375%.
  2. Aₒ = MTBF / (MTBF + MTTR + MDT)Additional downtime brings operational availability to 99.99500025%.
  3. Downtime/yr = 8,760 (1 − Aₒ)Annual downtime is 0.4379781 hours or 26.27869 minutes.
  4. A(t) = Aᵢ + (1−Aᵢ) exp[−(1/MTBF + 1/MTTR)t]Starting fully up, transient availability at 24 h is 99.999375%.

Model assumptions

MTBF is mean uptime, excluding downtime. Enter only additional preventive and logistics downtime per uptime cycle in MDT. The two-state Markov model uses exponential up and repair durations.

Method and sources

Related examples