Strong concrete, thin trial

Test whether higher flexural strength makes a thin trial practical on a busy connector.

Design readout

Required D
9.41
in
Trial D
8.25
in
Depth margin
-1.16
in
Life ratio
0.44
×

Doweled JPCP section

Doweled JPCP sectionJOINT SECTIONLOAD TRANSFERTRANSVERSE JOINTSLABDOWELDTRIAL D8.25 inREQUIRED D9.41 inSUPPORT K120 pci
Section cut across a transverse joint. Dowel dimensions and spacing follow the governing agency detail.

Trial slab below target

Marker shows trial thickness relative to the AASHTO thickness requirement.

Calculation ledger
Trial design traffic capacity
4,623,788 ESAL
Trial ESAL margin
-5,876,212 ESAL
Serviceability loss ΔPSI
1.9
Reliability deviate Zᵣ
-1.282

Inputs

Changes update results

Design demand
ESAL
Concrete and foundation
psi
ksi
pci
in

Work through this example

  1. Enter traffic, serviceability, concrete properties and effective support.
  2. Solve the rigid design equation on the increasing thickness branch.
  3. Evaluate the trial slab against the required thickness and compute allowable design traffic.

Use the thickness margin to see how much additional depth the trial needs.

The life ratio compares AASHTO serviceability-based traffic capacity with design demand. A separate fatigue, erosion or faulting analysis requires project-specific data.

Read the equations and sources