Baghouse air-to-cloth & filter count

Size pulse-jet, shaker and cartridge collectors using net media area and interstitial can velocity.

Inputs

Collector duty
CFM
ft/min
Use 0 for the midpoint of the screening band. Enter the supplier’s design ratio when available.
Filter & housing
in
ft
Use 0 to size the online count.
ft²
FPM
Use the collector supplier’s limit for this dust.

Live results

Collector air path and media loading

Collector air path and media loadingEXHAUST FLOW12,000CFMAIR-TO-CLOTH6.945ft/minONLINE COUNT110unitsCAN VELOCITY163.5FPMDusty inletFiltered airPulse jetCan velocityOperating air-to-clothBand 5 ft/min6.945 ft/minHigh 9 ft/min
Dusty air enters from the left and passes around the elements. Filtered air exits from the upper plenum.

Air-to-cloth and interstitial velocity are within the entered screening limits.

Exhaust flow
12,000 CFM
Air-to-cloth
6.94494 ft/min
Online count
110 units
Can velocity
163.484 FPM

Media and screening band

Minimum required media
1,714.29 ft²
Media per element
15.708 ft²
Installed online media
1,727.88 ft²
Recommended online count
110 units
Design air-to-cloth
7 ft/min
Actual ratio in alternate units
2.11682 m/min
Screening band low
5 ft/min
Screening band high
9 ft/min

Can cross-section

Free can area
73.4016 ft²
Can velocity
163.484 FPM
Entered can velocity limit
250 FPM

Equations and assumptions

Media sizing

A_min = Q ÷ (A/C)_design · N_min = ceil(A_min ÷ A_element)

A bag uses the cylindrical length × circumference. Enter the rated pleated media area for a cartridge and its outside diameter separately. Count only filters online during the airflow condition.

Operating air-to-cloth

(A/C)_actual = Q ÷ (N_online × A_element)

CFM per ft² reduces to ft/min. The selectable material and collector bands are preliminary screening estimates informed by industry practice and EPA gas-to-cloth examples. Request vendor values for loading, moisture and cleaning method.

Interstitial can velocity

V_can = Q ÷ (A_can − N_online × π × D² ÷ 4)

Use gross cross-section where upward gas passes the installed elements. Equipment with downflow or crossflow needs a geometry-specific check. A nonpositive net area means the entered elements do not fit this section.

References

Worked examples