Overcrowded collector housing

An entered bag count physically consumes the full gross can cross-section.

Inputs

Collector duty
CFM
ft/min
Use 0 for the midpoint of the screening band. Enter the supplier’s design ratio when available.
Filter & housing
in
ft
Use 0 to size the online count.
ft²
FPM
Use the collector supplier’s limit for this dust.

Live results

Collector air path and media loading

Collector air path and media loadingEXHAUST FLOW6,500CFMAIR-TO-CLOTH2.612ft/minONLINE COUNT96unitsCAN VELOCITYNo areaDusty inletFiltered airPulse jetBlocked sectionOperating air-to-clothBand 4 ft/min2.612 ft/minHigh 8 ft/min
Dusty air enters from the left and passes around the elements. Filtered air exits from the upper plenum.

Operating air-to-cloth is below the selected screening band.

Installed elements consume the full can cross-section. Review the housing geometry.

Exhaust flow
6,500 CFM
Air-to-cloth
2.61239 ft/min
Online count
96 units
Can velocity
No free area

Media and screening band

Minimum required media
1,083.33 ft²
Media per element
25.9181 ft²
Installed online media
2,488.14 ft²
Recommended online count
42 units
Design air-to-cloth
6 ft/min
Actual ratio in alternate units
0.796257 m/min
Screening band low
4 ft/min
Screening band high
8 ft/min

Can cross-section

Free can area
-2.4115 ft²
Can velocity
No free area
Entered can velocity limit
250 FPM

Worked calculation at the starting values

A nonpositive free section invalidates interstitial velocity. Review the entered count, diameter and housing geometry.

  1. Required media = 3.067658 ÷ 0.03048 = 100.645 m².
  2. Sized online count = round up (100.645 ÷ 2.407874) = 42.
  3. Installed free can area = 3.716122 − 96 × π × 0.2286² ÷ 4 = -0.2240358 m².
Starting result snapshot
Exhaust flow
6,500 CFM
Air-to-cloth
2.61239 ft/min
Online count
96 units
Can velocity
No free area

Equations and assumptions

Media sizing

A_min = Q ÷ (A/C)_design · N_min = ceil(A_min ÷ A_element)

A bag uses the cylindrical length × circumference. Enter the rated pleated media area for a cartridge and its outside diameter separately. Count only filters online during the airflow condition.

Operating air-to-cloth

(A/C)_actual = Q ÷ (N_online × A_element)

CFM per ft² reduces to ft/min. The selectable material and collector bands are preliminary screening estimates informed by industry practice and EPA gas-to-cloth examples. Request vendor values for loading, moisture and cleaning method.

Interstitial can velocity

V_can = Q ÷ (A_can − N_online × π × D² ÷ 4)

Use gross cross-section where upward gas passes the installed elements. Equipment with downflow or crossflow needs a geometry-specific check. A nonpositive net area means the entered elements do not fit this section.