Prefilter-protected HEPA

A protected HEPA installation shows a relatively low measured pressure rise.

Inputs

Airflow & filter loading
CFM
in.wg
in.wg
in.wg/1k h
Pressure rise per 1,000 operating hours at rated flow.
%
Operating & replacement cost
/kWh
h
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Filter loading and annual cost curve

Filter loading and annual cost curveAVG. FAN POWER0.1388kWANNUAL ENERGY104.4USDANNUAL CHANGES44.76USDECONOMIC ΔP1.484in.wgFilter loading over timeTotal annual costClean15,230 hChange-out ΔPEconomic pressure vs change-out capClean 0.3814 in.wg1.484 in.wgCap 1.726 in.wg
The loading plot shows pressure rise across the modeled cycle. The cost curve combines energy with annualized replacement spend.

The cost curve favors a change-out below the current pressure cap.

Avg. fan power
0.138838 kW
Annual energy
104.406 USD
Annual changes
44.7552 USD
Economic ΔP
1.48371 in.wg

Current change-out

Average filter pressure drop
1.05384 in.wg
Extra power from loading
0.0885919 kW
Operating hours per filter
15,227.3 h
Annual filtration energy
2.22655 MMBtu
Total current annual cost
149.161 USD

Economic threshold

Unconstrained change-out
1.48371 in.wg
Constrained change-out
1.48371 in.wg
Optimal operating hours per filter
12,480.7 h
Optimized annual cost
146.994 USD
Modeled annual savings
2.16749 USD

Worked calculation at the starting values

Lower loading extends the modeled service interval. Inspect the annualized result and any independent calendar life limit.

  1. Average filter pressure = (95 + 430) ÷ 2 = 262.5 Pa.
  2. Current annual total = 104.4062 + 44.75522 = 149.1614 USD.
  3. Modeled change-out at 369.5749 Pa gives 146.9939 USD per year.
Starting result snapshot
Avg. fan power
0.138838 kW
Annual energy
104.406 USD
Annual changes
44.7552 USD
Economic ΔP
1.48371 in.wg

Equations and assumptions

Average filtration power

ΔP_avg = ΔP_clean + x ÷ 2 · kW = Q × ΔP_avg ÷ (1000 × η)

x is the allowed pressure rise above clean. Q is m³/s and pressure is Pa. Constant airflow, uniform loading and fixed combined efficiency are assumed.

Annualized cost

C_year = H × [kW × c + C_r × r ÷ x]

H is annual operating hours, c is price per kWh, C_r is hardware plus labor per change and r is the measured pressure rise per operating hour. Expected changes per year can be fractional.

Economic change-out pressure

x* = √(2 × C_r × r ÷ [c × Q ÷ (1000 × η)])

Add x* to the clean pressure for the unconstrained threshold. The selected economic change-out is capped by the entered pressure limit. Validate system airflow, leaks, efficiency, contamination, service life and manufacturer limits with field measurements.