Cooling-dominant laboratory

A hot-climate lab screens sash savings with a large sensible cooling requirement.

Inputs

Hood opening
ft
in
in
FPM
Control & schedule
%
Percent of working exhaust. Also applies as the occupied minimum.
h
Make-up air utilities
°F·h
°F·h
Decimal delivered-to-input ratio.
/kWh
/kWh
Enter both prices in the selected currency. Currency selection changes labels.

Live results

Sash positions and annual cost

Sash positions and annual costWORKING FLOW675CFMREDUCED FLOW375CFMENERGY SAVED7.149MMBtuCOST SAVED478USDSash openingsMake-up air cost / yearWorking18 inReduced10 inWorking1,449 USDReduced970.5 USDReduced sash flow vs workingReduced flow375 CFMWork 675 CFM
Sash openings follow the entered heights. The bars compare annual sensible make-up air costs for the two positions.

The sash comparison uses a shared VAV minimum. Verify containment at both operating positions.

Working flow
675 CFM
Reduced flow
375 CFM
Energy saved
7.14898 MMBtu
Cost saved
478.003 USD

Airflow and face velocity

Working face velocity
90 FPM
Reduced face velocity
90 FPM
Unoccupied exhaust
236.25 CFM
Annual mean flow, working
456.627 CFM
Annual mean flow, reduced
305.942 CFM

Make-up air per year

Working heating input
2.95897 MMBtu
Working cooling input
18.7049 MMBtu
Working total energy
21.6639 MMBtu
Reduced total energy
14.5149 MMBtu
Working annual cost
1,448.51 USD
Reduced annual cost
970.509 USD

Worked calculation at the starting values

Cooling COP converts delivered load to input energy. Humidity and latent cooling need a separate analysis.

  1. Working flow = 1.524 × 0.4572 × 0.4572 = 0.3185645 m³/s.
  2. Average flow with managed sash = 0.1443884 m³/s including 0.1114976 m³/s during unoccupied hours.
  3. Sash savings = 1,448.513 − 970.5094 = 478.0032 USD per year.
Starting result snapshot
Working flow
675 CFM
Reduced flow
375 CFM
Energy saved
7.14898 MMBtu
Cost saved
478.003 USD

Equations and assumptions

Face velocity and sash flow

Q = W × H × V_face

Use the unobstructed opening. ANSI/ASSP Z9.5 practice uses 80–100 FPM as a starting range where appropriate. Select a site-specific target after containment testing.

VAV and bypass operation

Q_reduced = max(W × H_reduced × V_face, Q_min)

VAV uses the entered minimum whenever the sash demand falls below it and during all unoccupied hours. The CAV/bypass comparison keeps working flow throughout. The same unoccupied minimum applies to both sash scenarios.

Annual sensible make-up energy

E_heat = 1.2072 × Q_mean × H_DH ÷ η · E_cool = 1.2072 × Q_mean × C_DH ÷ COP

Q_mean is the occupied/unoccupied average in m³/s. Enter degree-hours as the sum of temperature differences over hours, not HDD/CDD in degree-days. The result is purchased kWh, with an MMBtu energy-equivalent display. The model assumes similar climate-hour distribution across shifts and excludes latent loads, fans and heat recovery.