Walk-in box heat load
Use consistent energy and time units. One refrigeration ton is 12,000 BTU/h. Confirm equipment at the selected evaporating and condensing conditions.
Review the engineering conventions, reference data, validation limits and unit definitions behind the ColdChainLab calculators.
All equations use metric working quantities internally. The readout can switch to US customary units without changing the physical inputs. Temperature differences use a factor of 1.8 without a 32-degree offset. Pressure diagnostics convert gauge readings to absolute pressure before using saturation data.
Commercial room loads distinguish transmission, door air exchange, product cooling, and heat from equipment and people. An air-change input represents estimated door exchange volume. Use observed door use or a detailed infiltration method to validate it.
Use consistent energy and time units. One refrigeration ton is 12,000 BTU/h. Confirm equipment at the selected evaporating and condensing conditions.
For E in kJ and Q in kW the answer is hours. Pack geometry, access to air, and surface/core gradients are folded into one estimated effectiveness. Validate core temperatures with probes under the intended loading.
The Honeywell R-448A table covers 100–2,900 kPa absolute and is interpolated in ln(P). The other curves invert the CoolProp ancillary pressure fits shown above. Temperatures in this equation are absolute. Check the observed detail range and verify with supplier charts for final service decisions.
Budget for seams, bridges, air exchange, payload preconditioning, and ambient extremes. Verify the actual pack-out by an instrumented test against its approved qualification protocol and payload limits.
This screen assumes compressor input heat reaches the condenser. Air properties are 1.20 kg/m³ and 1.006 kJ/(kg·K). Water properties are 997 kg/m³ and 4.186 kJ/(kg·K).
Apple, early potato, and lettuce coefficients use ASHRAE tabulated reference values or close commodity proxies. The strawberry and broccoli coefficients are illustrative. The TD bands reflect high-humidity starting points. Confirm coil, airflow, control, and packaging effects with the supplier.
Water reference properties are at 20 °C. The pressure factor compares fully developed laminar flow in the same pipe at the resized flow. Turbulent pipe, coil, and fitting losses need their own hydraulic calculations.
Peak adds the compressor, active heater, and auxiliaries if they run together. With staging, the compressor draw must cover its daily energy and defrost recovery during the heater-off hours. If that requires more than rated draw, the staged peak is unavailable. The tariff estimate covers energy charges.
CoolProp coefficients are included under the MIT license. The calculator carries these data in its local files.
Confirm project acceptance criteria with the responsible engineer, equipment supplier, and quality team.
A refrigeration ton is 12,000 BTU per hour, or approximately 3.51685 kW of cooling capacity. The produce calculator uses short tons or metric tonnes for produce mass.
Open the tool’s formulas and references. The output breakdown shows the intermediate terms. Export JSON for the input and output values in their stored units.