A copper coupon exposed over 33 cm² lost 192 mg in a 336-hour circulation trial.

Inputs

SI units

Use cleaned mass loss, total exposed area and the actual exposure duration. Equivalent weights in the presets are illustrative.

mg
cm²
hr
g/cm³
g/equiv
Penetration
0.17 mm/yr
Areal loss
4.16 g/(m²·day)
Current equiv.
14.6 µA/cm²
US rate
6.68 mpy

Coupon exposure cell

Schematic
Coupon exposure cell (schematic, not to scale)Exposure bathNet metal lossExposed coupon facesMASS LOSS192 mgEXPOSURE336 hrAREAL LOSS4.16 g/(m²·day)
Average penetration

Compare with the project limit and inspect for pits. Localized attack can exceed the coupon average.

Reference scale · 0 to 1 mm/yr

Calculation details

Metric penetration
0.1697 mm/yr
US penetration
6.6824 mpy
Areal mass-loss rate
4.16 g/(m²·day)
Equivalent corrosion current
14.6 µA/cm²
mm/yr per µA/cm²
0.011621

Worked calculation

Starting values · SI
  1. 0.192 g ÷ (33 cm² × 336 hr) gives 0.00002 g/(cm²·hr).
  2. Multiply the mass flux by 87,600 ÷ 8.94 to get 0.16967 mm/yr. The G1 mpy constant gives 6.68236 mpy.
  3. The equivalent current density is 14.60115 µA/cm².

Document the effective copper valence used for the equivalent-current interpretation. The mass-loss result uses density and exposure independently.

Method and limits

  1. Normalize the exposure

    Use mass loss W in grams, total exposed area A in cm², duration T in hours and density ρ in g/cm³. Include both faces and edges if these were exposed.

  2. Calculate penetration and areal loss

    Average penetration = K × W ÷ (A × T × ρ). K is 87,600 for mm/yr and 3,450,000 for mpy. Areal mass loss = 240,000 × W ÷ (A × T) in g/(m²·day). The two published K values are independently rounded.

  3. Convert using equivalent weight

    The Faraday relation is mm/yr = 0.00327 × i × EW/ρ, where i is in µA/cm². Divide by the coefficient to convert back. In either Faraday mode, mpy = mm/yr ÷ 0.0254.