Vertical array in low-resistivity soil
A low-resistivity trench survey indicates 7.5 Ω·m at the proposed depth. The design current is 28 A.
Inputs
SI unitsUse surrounding soil resistivity. For low-resistance coke backfill, the optional effective diameter is the column outside diameter.
- Groundbed
- 0.235 Ω
- Single anode
- 1.549 Ω
- Crowding
- 1.36 ×
- Bed drop
- 6.58 V
Anode field and interaction
SchematicVerify field resistivity, backfill contact and actual current distribution before sizing a rectifier.
Calculation details
- Effective anode diameter
- 0.18 m
- Ideal parallel resistance
- 0.1721 Ω
- Mutual resistance term
- 0.0628 Ω
- Total modeled resistance
- 0.2349 Ω
- Target minus modeled resistance
- 0.7651 Ω
- Ideal-parallel efficiency
- 73.27 %
Inputs used
- Groundbed layout
- Vertical shallow row
- Soil resistivity
- 7.5 Ω·m
- Effective length
- 3 m
- Bare anode diameter
- 0.075 m
- Coke column diameter
- 0.18 m
- Anodes in parallel
- 9
- Center spacing
- 7.5 m
- Design current
- 28 A
- Resistance target
- 1 Ω
Worked calculation
Starting values · SI- The single electrode has 1.54892 Ω using the vertical geometry and 0.18 m effective diameter.
- Ideal parallel resistance is 0.1721 Ω. Adding 0.0628 Ω gives 0.2349 Ω.
- At 28 A, groundbed voltage drop is 6.57725 V.
Read the bed voltage drop at proposed operating current and carry this value to the rectifier calculation.
Method and limits
Estimate a single anode
For a shallow vertical electrode, R = ρ[ln(8L/d) − 1]/(2πL). Use the conductive coke column diameter and length when it functions as an equivalent electrode.
Apply trench depth if horizontal
With centerline depth h, set s = 2h and q = √(s² + L²). Dwight’s horizontal bracket is ln[4L(L + q)/(d × s)] + (s − q)/L − 1. Multiply by ρ/(2πL).
Estimate row interaction
With N > 1, add ρ × ln(0.656N)/(πNS) to R_single/N for center spacing S. This Sunde term is for a vertical row. Applying it to parallel horizontal trenches is an approximation. The voltage drop is design current × modeled bed resistance.