Vertical array in low-resistivity soil

A low-resistivity trench survey indicates 7.5 Ω·m at the proposed depth. The design current is 28 A.

Inputs

SI units

Use surrounding soil resistivity. For low-resistance coke backfill, the optional effective diameter is the column outside diameter.

Ω·m
m
m
m
m
A
Ω
Groundbed
0.235 Ω
Single anode
1.549 Ω
Crowding
1.36 ×
Bed drop
6.58 V

Anode field and interaction

Schematic
Anode field and interaction (schematic, not to scale)Vertical row4 of 9 anodesEFFECTIVE Ø0.18 mCENTER SPACING7.5 mROW RESISTANCE0.235 Ω
Within resistance target

Verify field resistivity, backfill contact and actual current distribution before sizing a rectifier.

Modeled resistance ÷ selected target

Calculation details

Effective anode diameter
0.18 m
Ideal parallel resistance
0.1721 Ω
Mutual resistance term
0.0628 Ω
Total modeled resistance
0.2349 Ω
Target minus modeled resistance
0.7651 Ω
Ideal-parallel efficiency
73.27 %

Worked calculation

Starting values · SI
  1. The single electrode has 1.54892 Ω using the vertical geometry and 0.18 m effective diameter.
  2. Ideal parallel resistance is 0.1721 Ω. Adding 0.0628 Ω gives 0.2349 Ω.
  3. At 28 A, groundbed voltage drop is 6.57725 V.

Read the bed voltage drop at proposed operating current and carry this value to the rectifier calculation.

Method and limits

  1. Estimate a single anode

    For a shallow vertical electrode, R = ρ[ln(8L/d) − 1]/(2πL). Use the conductive coke column diameter and length when it functions as an equivalent electrode.

  2. Apply trench depth if horizontal

    With centerline depth h, set s = 2h and q = √(s² + L²). Dwight’s horizontal bracket is ln[4L(L + q)/(d × s)] + (s − q)/L − 1. Multiply by ρ/(2πL).

  3. Estimate row interaction

    With N > 1, add ρ × ln(0.656N)/(πNS) to R_single/N for center spacing S. This Sunde term is for a vertical row. Applying it to parallel horizontal trenches is an approximation. The voltage drop is design current × modeled bed resistance.