Single bare Dwight anode
A test installation uses one 4 m bare anode, 0.09 m in diameter, in 21 Ω·m soil.
Inputs
SI unitsUse surrounding soil resistivity. For low-resistance coke backfill, the optional effective diameter is the column outside diameter.
- Groundbed
- 4.072 Ω
- Single anode
- 4.072 Ω
- Crowding
- 1 ×
- Bed drop
- 20.36 V
Anode field and interaction
SchematicReview soil resistivity, electrode spacing and effective backfill dimensions before relying on this layout.
Calculation details
- Effective anode diameter
- 0.09 m
- Ideal parallel resistance
- 4.0723 Ω
- Mutual resistance term
- 0 Ω
- Total modeled resistance
- 4.0723 Ω
- Target minus modeled resistance
- -3.0723 Ω
- Ideal-parallel efficiency
- 100 %
Inputs used
- Groundbed layout
- Vertical shallow row
- Soil resistivity
- 21 Ω·m
- Effective length
- 4 m
- Bare anode diameter
- 0.09 m
- Coke column diameter
- —
- Anodes in parallel
- 1
- Center spacing
- 0 m
- Design current
- 5 A
- Resistance target
- 1 Ω
Worked calculation
Starting values · SI- The single electrode has 4.07227 Ω using the vertical geometry and 0.09 m effective diameter.
- Ideal parallel resistance is 4.07227 Ω. Adding 0 Ω gives 4.07227 Ω.
- At 5 A, groundbed voltage drop is 20.36135 V.
With a single electrode, the mutual term is zero and groundbed resistance equals Dwight single-anode resistance.
Method and limits
Estimate a single anode
For a shallow vertical electrode, R = ρ[ln(8L/d) − 1]/(2πL). Use the conductive coke column diameter and length when it functions as an equivalent electrode.
Apply trench depth if horizontal
With centerline depth h, set s = 2h and q = √(s² + L²). Dwight’s horizontal bracket is ln[4L(L + q)/(d × s)] + (s − q)/L − 1. Multiply by ρ/(2πL).
Estimate row interaction
With N > 1, add ρ × ln(0.656N)/(πNS) to R_single/N for center spacing S. This Sunde term is for a vertical row. Applying it to parallel horizontal trenches is an approximation. The voltage drop is design current × modeled bed resistance.