DataCenterPUELab

Airside / waterside economizer savings calculator

Model free, partial and mechanical cooling hours and their annual MWh, energy cost and grid emissions.

Engineering schematic

Annual climate-bin dispatch

Live
Annual climate-bin dispatch FREE HOURS 3,500 h. ENERGY SAVE 1,007 MWh. COST SAVE 121k $. CO₂E AVOID 352.5 t CO₂e. See the results table for the full readout. FREE HOURS3,500hENERGY SAVE1,007MWhCOST SAVE121k$CO₂E AVOID352.5t CO₂e 800-3°1,2005°1,50010°1,80015°1,70021°1,76028°Full-freePartialMechanical°CEquivalent full-free cooling / year0%43% freeLimit 100%

3,800 h of equivalent full-free cooling per year.

Inputs

Operating limits
°C
°C
K
K
Load and utility rates
kWₜₕ
kW/kWₜₕ
kW/kWₜₕ
$/kWh
g/kWh
Annual climate bins

Enter six representative outdoor temperatures and annual hours. Any unentered hours, including lockouts, use mechanical cooling.

BinWet-bulbAnnual hours1
°C
h
2
°C
h
3
°C
h
4
°C
h
5
°C
h
6
°C
h

Calculation details

MeasureValue
Full-free outdoor cutoff10 °C
Mechanical cooling threshold16 °C
Full-free cooling hours3,500 h
Partial cooling hours1,800 h
Mechanical cooling hours3,460 h
Unentered hours assigned to mechanical0 h
Equivalent full-free cooling hours3,800 h
All-mechanical baseline energy2,847 MWh
Energy in full-free bins210 MWh
Energy in partial bins505.5 MWh
Energy in mechanical bins1,124.5 MWh
Modeled annual cooling energy1,840 MWh
Annual cooling energy savings1,007 MWh
Baseline cooling energy saved35.37 %
Annual energy cost savings120,840 $
Annual grid emissions avoided352.45 t CO₂e

Calculation method

  • Full-free cutoff = applicable setpoint − total approach
  • Partial-free fraction = (full-free cutoff + band − bin temperature) ÷ band
  • Annual MWh = Σ(cooling kW × mode input ratio × hours) ÷ 1,000

Airside uses outdoor dry-bulb against the IT inlet setpoint. Waterside uses outdoor wet-bulb against chilled-water supply. Partial cooling linearly blends both plant intensities. Missing climate hours are assigned to mechanical cooling in an 8,760-hour year.

Engineering limits

ASHRAE A1/A2 recommended inlet temperature spans 18–27 °C. At reference elevation, dry-bulb allowable limits are 15–32 °C for A1 and 10–35 °C for A2. Apply equipment, humidity, contamination and elevation limits when screening outdoor hours. Include relevant fans and pumps in both plant intensities.

Worked examples