UPS battery bank & Peukert runtime calculator

Estimate lead-acid string count, end-of-discharge runtime, UPS heat and time to recover 90% of discharged amp-hours.

Engineering schematic

DC battery bus & inverter

Live
DC battery bus & inverter RUN TIME 31.7 min. DC DRAW 620 A. STRINGS REQ 2. UPS HEAT 10.4 kW. See the results table for the full readout. RUN TIME31.7minDC DRAW620ASTRINGS REQ2UPS HEAT10.4kW Battery bank4 strings420 VInverterIT load250 kWRecharge path · 80 ATarget runtime / modeled autonomy0%32% usedLimit 100%

Runtime headroom 21.7 min

Inputs

UPS and DC bus
kW
%
V/cell
min
Lead-acid battery bank

Use the charger current available to the battery bank while the UPS serves the load.

Ah
A
%

Calculation details

MeasureValue
Series cells per string240 cells
End-of-discharge bus voltage420 V
Inverter DC input260.42 kW
Bank discharge current at cutoff620.04 A
Discharge current per installed string155.01 A
Installed bank capacity at C20600 Ah
Bank C20 reference current30 A
Minimum modeled C20 bank capacity229.51 Ah
Parallel strings required for target2 strings
Modeled autonomy at entered load31.68 min
Runtime headroom against target21.68 min
UPS inverter heat10.42 kW
UPS inverter heat35,543 Btu/h
Amp-hours withdrawn in modeled discharge327.41 Ah
Bulk charge time to recover 90% of withdrawn Ah4.33 h

Calculation method

  • Idc = IT kW × 1,000 ÷ (ηinv × cell count × Vcutoff)
  • Peukert hours = 20 × [(bank C20 ÷ 20) ÷ Idc]ᵏ
  • Charge recovery hours = 0.90 × Ah withdrawn ÷ (charger A × charge efficiency)

The nominal 480 V or 540 V bus uses 240 or 270 nominal 2 V cells in series per string. Current is held at the calculated end-of-discharge value. Runtime is capped at the nominal amp-hour limit at low current. Recharge assumes a constant available charger current during bulk charge.

Engineering limits

Use vendor constant-power discharge tables, temperature and aging corrections, and the full duty cycle for IEEE 485 sizing. The estimate covers lead-acid batteries. Recovery time refers to amp-hours withdrawn in the modeled discharge, with charger taper and float omitted.