DataCenterPUELab

High-rate discharge string count

A 750 kW load, 160 Ah strings and exponent 1.26 test a short high-current ride-through period.

Engineering schematic

DC battery bus & inverter

Live
DC battery bus & inverter RUN TIME 7.2 min. DC DRAW 1,860.1 A. STRINGS REQ 8. UPS HEAT 31.3 kW. See the results table for the full readout. RUN TIME7.2minDC DRAW1,860.1ASTRINGS REQ8UPS HEAT31.3kW Battery bank4 strings420 VInverterIT load750 kWRecharge path · 150 ATarget runtime / modeled autonomy0%209% usedLimit 100%

Runtime headroom -7.8 min

Inputs

UPS and DC bus
kW
%
V/cell
min
Lead-acid battery bank

Use the charger current available to the battery bank while the UPS serves the load.

Ah
A
%

Calculation details

MeasureValue
Series cells per string240 cells
End-of-discharge bus voltage420 V
Inverter DC input781.25 kW
Bank discharge current at cutoff1,860.12 A
Discharge current per installed string465.03 A
Installed bank capacity at C20640 Ah
Bank C20 reference current32 A
Minimum modeled C20 bank capacity1,148.63 Ah
Parallel strings required for target8 strings
Modeled autonomy at entered load7.18 min
Runtime headroom against target-7.82 min
UPS inverter heat31.25 kW
UPS inverter heat106,629 Btu/h
Amp-hours withdrawn in modeled discharge222.56 Ah
Bulk charge time to recover 90% of withdrawn Ah1.57 h

Starting calculation

  1. Multiply 240 cells by 1.75 V to get 420 V at cutoff. The inverter draws 1,860.12 A DC at this voltage.
  2. Apply Peukert’s exponent to 640 Ah of C20 capacity. The model gives 7.18 minutes and requires 8 strings for the target.

Compare the calculated minimum string count with installed strings. The estimate reflects the effect of the entered exponent at high current.

Calculation method

  • Idc = IT kW × 1,000 ÷ (ηinv × cell count × Vcutoff)
  • Peukert hours = 20 × [(bank C20 ÷ 20) ÷ Idc]ᵏ
  • Charge recovery hours = 0.90 × Ah withdrawn ÷ (charger A × charge efficiency)

The nominal 480 V or 540 V bus uses 240 or 270 nominal 2 V cells in series per string. Current is held at the calculated end-of-discharge value. Runtime is capped at the nominal amp-hour limit at low current. Recharge assumes a constant available charger current during bulk charge.

Engineering limits

Use vendor constant-power discharge tables, temperature and aging corrections, and the full duty cycle for IEEE 485 sizing. The estimate covers lead-acid batteries. Recovery time refers to amp-hours withdrawn in the modeled discharge, with charger taper and float omitted.