540 V DC bus at a 1.70 V cell cutoff

The nominal 540 V bus is supplying a 360 kW inverter load at the selected cell cutoff voltage.

Engineering schematic

DC battery bus & inverter

Live
DC battery bus & inverter RUN TIME 25.2 min. DC DRAW 825.6 A. STRINGS REQ 3. UPS HEAT 18.9 kW. See the results table for the full readout. RUN TIME25.2minDC DRAW825.6ASTRINGS REQ3UPS HEAT18.9kW Battery bank4 strings459 VInverterIT load360 kWRecharge path · 80 ATarget runtime / modeled autonomy0%48% usedLimit 100%

Runtime headroom 13.2 min

Inputs

UPS and DC bus
kW
%
V/cell
min
Lead-acid battery bank

Use the charger current available to the battery bank while the UPS serves the load.

Ah
A
%

Calculation details

MeasureValue
Series cells per string270 cells
End-of-discharge bus voltage459 V
Inverter DC input378.95 kW
Bank discharge current at cutoff825.59 A
Discharge current per installed string206.4 A
Installed bank capacity at C20660 Ah
Bank C20 reference current33 A
Minimum modeled C20 bank capacity355.74 Ah
Parallel strings required for target3 strings
Modeled autonomy at entered load25.19 min
Runtime headroom against target13.19 min
UPS inverter heat18.95 kW
UPS inverter heat64,651 Btu/h
Amp-hours withdrawn in modeled discharge346.65 Ah
Bulk charge time to recover 90% of withdrawn Ah4.59 h

Starting calculation

  1. Multiply 270 cells by 1.7 V to get 459 V at cutoff. The inverter draws 825.59 A DC at this voltage.
  2. Apply Peukert’s exponent to 660 Ah of C20 capacity. The model gives 25.19 minutes and requires 3 strings for the target.

Read the cutoff voltage and current together. At fixed DC power, current rises as battery voltage falls.

Calculation method

  • Idc = IT kW × 1,000 ÷ (ηinv × cell count × Vcutoff)
  • Peukert hours = 20 × [(bank C20 ÷ 20) ÷ Idc]ᵏ
  • Charge recovery hours = 0.90 × Ah withdrawn ÷ (charger A × charge efficiency)

The nominal 480 V or 540 V bus uses 240 or 270 nominal 2 V cells in series per string. Current is held at the calculated end-of-discharge value. Runtime is capped at the nominal amp-hour limit at low current. Recharge assumes a constant available charger current during bulk charge.

Engineering limits

Use vendor constant-power discharge tables, temperature and aging corrections, and the full duty cycle for IEEE 485 sizing. The estimate covers lead-acid batteries. Recovery time refers to amp-hours withdrawn in the modeled discharge, with charger taper and float omitted.