208 V rack on two 30 A whips

Two 30 A 208/120 V feeds share 6.7 kW of normal load. Check the most heavily loaded phase after transfer.

Engineering schematic

Wye A/B rack distribution

Live
Wye A/B rack distribution LIMIT / LEG 24 A. WORST LEG 22.4 A. NEUTRAL MAX 4.6 A. HEADROOM 1.6 A. See the results table for the full readout. LIMIT / LEG24AWORST LEG22.4ANEUTRAL MAX4.6AHEADROOM1.6A A whipN 2.7 AB whipN 1.9 A208/120 V WyeWorst survivorL122.4 AL219.3 AL317.1 ATick = breaker limitWorst surviving phase / continuous limit0%93% usedLimit 100%

Failover breaker headroom 1.6 A

Inputs

Breaker and supply

Enter the share on each phase that has a single cord and no independent transfer path.

A
%
A whip · normal load
kW
kW
kW
B whip · normal load
kW
kW
kW

Calculation details

MeasureValue
Total normal rack load6.7 kW
80% continuous limit per phase24 A
Highest phase current after failover22.37 A
Minimum continuous-breaker headroom1.63 A
Highest fundamental neutral current4.58 A
Balanced real-power limit per whip8.21 kW
A normal · L111.4 A
A normal · L29.65 A
A normal · L38.33 A
B normal · L110.96 A
B normal · L29.65 A
B normal · L38.77 A
A surviving · L122.37 A
A surviving · L219.3 A
A surviving · L317.11 A
B surviving · L122.37 A
B surviving · L219.3 A
B surviving · L317.11 A
A normal · neutral2.67 A
B normal · neutral1.91 A
A surviving · neutral4.58 A
B surviving · neutral4.58 A
A normal · phase imbalance16.42 %
B normal · phase imbalance11.94 %
A surviving · phase imbalance14.18 %
B surviving · phase imbalance14.18 %
Rack load shed on loss of A0 kW
Rack load shed on loss of B0 kW

Starting calculation

  1. Multiply the 30 A breaker rating by 0.80 to get 24 A continuous per phase.
  2. Convert each phase load at 120 V line-to-neutral and PF 0.95. The highest surviving phase reaches 22.37 A, giving 1.63 A headroom.

Evaluate each line-to-neutral phase. A total rack kW figure can hide a heavily loaded leg.

Calculation method

  • Iphase = 1,000 × kWphase ÷ (VLN × PF)
  • Ineutral = √(Ia² + Ib² + Ic² − IaIb − IbIc − IcIa)
  • Continuous current limit = 0.80 × breaker rating

Use nominal line-to-neutral voltage and phase-to-neutral real kW. Imbalance is largest deviation from the phase mean divided by that mean. Transferable loads from the failed whip are added to corresponding phases on the survivor. Non-transferable single-cord loads on the failed whip drop.

Engineering limits

The neutral model uses fundamental currents with a common power factor and 120° phase spacing. Check harmonic neutral current, conductor ampacity, breaker listing and local code separately. The screen uses 80% of a standard-rated breaker for a continuous load of three hours or more.