Three-phase rack PDU load balance calculator
Check A/B whip phase currents, Wye neutral load and failover headroom on 415/240 V or 208/120 V service.
Engineering schematic
Wye A/B rack distribution
Failover breaker headroom 1.9 A
Inputs
Calculation details
| Measure | Value |
|---|---|
| Total normal rack load | 14.6 kW |
| 80% continuous limit per phase | 25.6 A |
| Highest phase current after failover | 23.68 A |
| Minimum continuous-breaker headroom | 1.92 A |
| Highest fundamental neutral current | 3.59 A |
| Balanced real-power limit per whip | 17.51 kW |
| A normal · L1 | 11.4 A |
| A normal · L2 | 10.53 A |
| A normal · L3 | 9.21 A |
| B normal · L1 | 12.28 A |
| B normal · L2 | 10.09 A |
| B normal · L3 | 10.53 A |
| A surviving · L1 | 23.68 A |
| A surviving · L2 | 20.61 A |
| A surviving · L3 | 19.74 A |
| B surviving · L1 | 23.68 A |
| B surviving · L2 | 20.61 A |
| B surviving · L3 | 19.74 A |
| A normal · neutral | 1.91 A |
| B normal · neutral | 2.01 A |
| A surviving · neutral | 3.59 A |
| B surviving · neutral | 3.59 A |
| A normal · phase imbalance | 11.27 % |
| B normal · phase imbalance | 12 % |
| A surviving · phase imbalance | 10.96 % |
| B surviving · phase imbalance | 10.96 % |
| Rack load shed on loss of A | 0 kW |
| Rack load shed on loss of B | 0 kW |
Update the highlighted inputs to see the results.
Calculation method
- Iphase = 1,000 × kWphase ÷ (VLN × PF)
- Ineutral = √(Ia² + Ib² + Ic² − IaIb − IbIc − IcIa)
- Continuous current limit = 0.80 × breaker rating
Use nominal line-to-neutral voltage and phase-to-neutral real kW. Imbalance is largest deviation from the phase mean divided by that mean. Transferable loads from the failed whip are added to corresponding phases on the survivor. Non-transferable single-cord loads on the failed whip drop.
Engineering limits
The neutral model uses fundamental currents with a common power factor and 120° phase spacing. Check harmonic neutral current, conductor ampacity, breaker listing and local code separately. The screen uses 80% of a standard-rated breaker for a continuous load of three hours or more.
Worked examples
DataCenterPUELab · Calculation sheet
Three-phase rack PDU load balance calculator
Failover breaker headroom 1.9 A
Inputs
- Wye service
- 415 V / 240 V
- Breaker rating per whip
- 32 A
- Load power factor
- 0.95
- Non-transferable load
- 0 %
- A · L1
- 2.6 kW
- A · L2
- 2.4 kW
- A · L3
- 2.1 kW
- B · L1
- 2.8 kW
- B · L2
- 2.3 kW
- B · L3
- 2.4 kW
Results
- Total normal rack load
- 14.6 kW
- 80% continuous limit per phase
- 25.6 A
- Highest phase current after failover
- 23.68 A
- Minimum continuous-breaker headroom
- 1.92 A
- Highest fundamental neutral current
- 3.59 A
- Balanced real-power limit per whip
- 17.51 kW
- A normal · L1
- 11.4 A
- A normal · L2
- 10.53 A
- A normal · L3
- 9.21 A
- B normal · L1
- 12.28 A
- B normal · L2
- 10.09 A
- B normal · L3
- 10.53 A
- A surviving · L1
- 23.68 A
- A surviving · L2
- 20.61 A
- A surviving · L3
- 19.74 A
- B surviving · L1
- 23.68 A
- B surviving · L2
- 20.61 A
- B surviving · L3
- 19.74 A
- A normal · neutral
- 1.91 A
- B normal · neutral
- 2.01 A
- A surviving · neutral
- 3.59 A
- B surviving · neutral
- 3.59 A
- A normal · phase imbalance
- 11.27 %
- B normal · phase imbalance
- 12 %
- A surviving · phase imbalance
- 10.96 %
- B surviving · phase imbalance
- 10.96 %
- Rack load shed on loss of A
- 0 kW
- Rack load shed on loss of B
- 0 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.