A rack transfer switch allows single-cord loads to move to the surviving 415/240 V feed on matching phases.

Engineering schematic

Wye A/B rack distribution

Live
Wye A/B rack distribution LIMIT / LEG 32 A. WORST LEG 30.7 A. NEUTRAL MAX 2.7 A. HEADROOM 1.3 A. See the results table for the full readout. LIMIT / LEG32AWORST LEG30.7ANEUTRAL MAX2.7AHEADROOM1.3A A whipN 2.7 AB whipN 1.2 A415/240 V WyeWorst survivorL130.7 AL228.5 AL329.8 ATick = breaker limitWorst surviving phase / continuous limit0%96% usedLimit 100%

Failover breaker headroom 1.3 A

Inputs

Breaker and supply

Enter the share on each phase that has a single cord and no independent transfer path.

A
%
A whip · normal load
kW
kW
kW
B whip · normal load
kW
kW
kW

Calculation details

MeasureValue
Total normal rack load20.3 kW
80% continuous limit per phase32 A
Highest phase current after failover30.7 A
Minimum continuous-breaker headroom1.3 A
Highest fundamental neutral current2.74 A
Balanced real-power limit per whip21.89 kW
A normal · L116.67 A
A normal · L213.6 A
A normal · L314.47 A
B normal · L114.04 A
B normal · L214.91 A
B normal · L315.35 A
A surviving · L130.7 A
A surviving · L228.51 A
A surviving · L329.82 A
B surviving · L130.7 A
B surviving · L228.51 A
B surviving · L329.82 A
A normal · neutral2.74 A
B normal · neutral1.16 A
A surviving · neutral1.91 A
B surviving · neutral1.91 A
A normal · phase imbalance11.76 %
B normal · phase imbalance4.95 %
A surviving · phase imbalance3.94 %
B surviving · phase imbalance3.94 %
Rack load shed on loss of A0 kW
Rack load shed on loss of B0 kW

Starting calculation

  1. Multiply the 40 A breaker rating by 0.80 to get 32 A continuous per phase.
  2. Convert each phase load at 240 V line-to-neutral and PF 0.95. The highest surviving phase reaches 30.7 A, giving 1.3 A headroom.

The model assumes phase mapping is preserved. Confirm the actual transfer switch wiring and ratings.

Calculation method

  • Iphase = 1,000 × kWphase ÷ (VLN × PF)
  • Ineutral = √(Ia² + Ib² + Ic² − IaIb − IbIc − IcIa)
  • Continuous current limit = 0.80 × breaker rating

Use nominal line-to-neutral voltage and phase-to-neutral real kW. Imbalance is largest deviation from the phase mean divided by that mean. Transferable loads from the failed whip are added to corresponding phases on the survivor. Non-transferable single-cord loads on the failed whip drop.

Engineering limits

The neutral model uses fundamental currents with a common power factor and 120° phase spacing. Check harmonic neutral current, conductor ampacity, breaker listing and local code separately. The screen uses 80% of a standard-rated breaker for a continuous load of three hours or more.