208 V failover exceeds the continuous limit

On 208 V service, a 30 A breaker can carry the normal split but has a heavily loaded L1 after transfer.

Engineering schematic

Wye A/B rack distribution

Live
Wye A/B rack distribution LIMIT / LEG 24 A. WORST LEG 31.7 A. NEUTRAL MAX 13.5 A. HEADROOM -7.7 A. See the results table for the full readout. LIMIT / LEG24AWORST LEG31.7ANEUTRAL MAX13.5AHEADROOM-7.7A A whipN 7.1 AB whipN 6.8 A208/120 V WyeWorst survivorL131.7 AL219.5 AL317.2 ATick = breaker limitWorst surviving phase / continuous limit0%132% usedLimit 100%

Failover breaker headroom -7.7 A

Inputs

Breaker and supply

Enter the share on each phase that has a single cord and no independent transfer path.

A
%
A whip · normal load
kW
kW
kW
B whip · normal load
kW
kW
kW

Calculation details

MeasureValue
Total normal rack load7.55 kW
80% continuous limit per phase24 A
Highest phase current after failover31.7 A
Minimum continuous-breaker headroom-7.7 A
Highest fundamental neutral current13.5 A
Balanced real-power limit per whip7.95 kW
A normal · L116.3 A
A normal · L211.32 A
A normal · L38.15 A
B normal · L115.4 A
B normal · L28.15 A
B normal · L39.06 A
A surviving · L131.7 A
A surviving · L219.47 A
A surviving · L317.21 A
B surviving · L131.7 A
B surviving · L219.47 A
B surviving · L317.21 A
A normal · neutral7.12 A
B normal · neutral6.84 A
A surviving · neutral13.5 A
B surviving · neutral13.5 A
A normal · phase imbalance36.71 %
B normal · phase imbalance41.67 %
A surviving · phase imbalance39.07 %
B surviving · phase imbalance39.07 %
Rack load shed on loss of A0 kW
Rack load shed on loss of B0 kW

Starting calculation

  1. Multiply the 30 A breaker rating by 0.80 to get 24 A continuous per phase.
  2. Convert each phase load at 120 V line-to-neutral and PF 0.92. The highest surviving phase reaches 31.7 A, giving -7.7 A headroom.

Use the worst survivor leg and continuous rating. Balance the phase loads and check the new margin.

Calculation method

  • Iphase = 1,000 × kWphase ÷ (VLN × PF)
  • Ineutral = √(Ia² + Ib² + Ic² − IaIb − IbIc − IcIa)
  • Continuous current limit = 0.80 × breaker rating

Use nominal line-to-neutral voltage and phase-to-neutral real kW. Imbalance is largest deviation from the phase mean divided by that mean. Transferable loads from the failed whip are added to corresponding phases on the survivor. Non-transferable single-cord loads on the failed whip drop.

Engineering limits

The neutral model uses fundamental currents with a common power factor and 120° phase spacing. Check harmonic neutral current, conductor ampacity, breaker listing and local code separately. The screen uses 80% of a standard-rated breaker for a continuous load of three hours or more.