A contained aisle provides two high-flow grates under a 17 kW rack. The floor opening is limited by access space.

Engineering schematic

Underfloor plenum & rack

Live
Underfloor plenum & rack TILE FLOW 0.82 m³/s. OPEN AREA 56 %. STATIC ΔP 26 Pa. RACK LIMIT 25.8 kW. See the results table for the full readout. TILE FLOW0.82m³/sOPEN AREA56%STATIC ΔP26PaRACK LIMIT25.8kW Cold aisle0.82 m³/sIT rackRaised-floor plenum26 Pa2 installed · 2 requiredRack demand / delivered cooling0%66% usedLimit 100%

Rack load headroom 8.8 kW

Inputs

Tile and underfloor plenum
mm
mm
Pa
kg/m³
Air delivery to rack

The delivery fraction accounts for supply air that escapes the rack inlet.

kW
K
%

Calculation details

MeasureValue
Open area per tile0.2081 m²
Gross discharge per tile0.904 m³/s
Delivered airflow per tile0.823 m³/s
Delivered airflow across installed tiles1.646 m³/s
Airflow required at rack load1.083 m³/s
Minimum tiles per rack2 tiles
Maximum rack load at target ΔT25.82 kW
Rack load headroom8.82 kW

Starting calculation

  1. The tile opening is 0.2081 m². Apply its discharge coefficient at 26 Pa to obtain 0.904 m³/s gross per tile.
  2. After air delivery losses, one tile supplies 0.823 m³/s. Round the rack’s 1.083 m³/s requirement up to 2 tiles.

Check the modeled rack limit and local static pressure after both grates are installed.

Calculation method

  • Aopen = width × depth × open fraction
  • Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
  • Supported rack kW = useful rack airflow × ρ × cp × ΔT

The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.

Engineering limits

Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.