DataCenterPUELab

68% grate for a 25 kW rack

A rack uses three high-flow grates with a good seal between supply and return paths.

Engineering schematic

Underfloor plenum & rack

Live
Underfloor plenum & rack TILE FLOW 1.18 m³/s. OPEN AREA 68 %. STATIC ΔP 33 Pa. RACK LIMIT 59.8 kW. See the results table for the full readout. TILE FLOW1.18m³/sOPEN AREA68%STATIC ΔP33PaRACK LIMIT59.8kW Cold aisle1.18 m³/sIT rackRaised-floor plenum33 Pa3 installed · 2 requiredRack demand / delivered cooling0%42% usedLimit 100%

Rack load headroom 34.8 kW

Inputs

Tile and underfloor plenum
mm
mm
Pa
kg/m³
Air delivery to rack

The delivery fraction accounts for supply air that escapes the rack inlet.

kW
K
%

Calculation details

MeasureValue
Open area per tile0.2527 m²
Gross discharge per tile1.256 m³/s
Delivered airflow per tile1.18 m³/s
Delivered airflow across installed tiles3.541 m³/s
Airflow required at rack load1.479 m³/s
Minimum tiles per rack2 tiles
Maximum rack load at target ΔT59.84 kW
Rack load headroom34.84 kW

Starting calculation

  1. The tile opening is 0.2527 m². Apply its discharge coefficient at 33 Pa to obtain 1.256 m³/s gross per tile.
  2. After air delivery losses, one tile supplies 1.18 m³/s. Round the rack’s 1.479 m³/s requirement up to 2 tiles.

Large openings can change the plenum pressure itself. Rebalance and remeasure before relying on the constant-pressure estimate.

Calculation method

  • Aopen = width × depth × open fraction
  • Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
  • Supported rack kW = useful rack airflow × ρ × cp × ΔT

The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.

Engineering limits

Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.

Related worked examples