Raised-floor perforated tile airflow calculator
Estimate CFM per floor tile, tile count and supported rack kW from open area and plenum static pressure.
Engineering schematic
Underfloor plenum & rack
Rack load headroom 7.7 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Open area per tile | 0.1486 m² |
| Gross discharge per tile | 0.532 m³/s |
| Delivered airflow per tile | 0.452 m³/s |
| Delivered airflow across installed tiles | 1.357 m³/s |
| Airflow required at rack load | 0.828 m³/s |
| Minimum tiles per rack | 2 tiles |
| Maximum rack load at target ΔT | 19.66 kW |
| Rack load headroom | 7.66 kW |
Update the highlighted inputs to see the results.
Calculation method
- Aopen = width × depth × open fraction
- Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
- Supported rack kW = useful rack airflow × ρ × cp × ΔT
The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.
Engineering limits
Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.
Worked examples
DataCenterPUELab · Calculation sheet
Raised-floor perforated tile airflow calculator
Rack load headroom 7.7 kW
Inputs
- Open area
- 40% perforated
- Tile width
- 609.6 mm
- Tile depth
- 609.6 mm
- Plenum static pressure
- 20 Pa
- Discharge coefficient
- 0.62
- Air density
- 1.2 kg/m³
- Rack IT load
- 12 kW
- Target rack ΔT
- 12 K
- Tiles serving this rack
- 3
- Air reaching the rack
- 85 %
Results
- Open area per tile
- 0.1486 m²
- Gross discharge per tile
- 0.532 m³/s
- Delivered airflow per tile
- 0.452 m³/s
- Delivered airflow across installed tiles
- 1.357 m³/s
- Airflow required at rack load
- 0.828 m³/s
- Minimum tiles per rack
- 2 tiles
- Maximum rack load at target ΔT
- 19.66 kW
- Rack load headroom
- 7.66 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.