No positive plenum pressure

A stopped supply fan leaves zero measured pressure across the perforated tile.

Engineering schematic

Underfloor plenum & rack

Live
Underfloor plenum & rack TILE FLOW 0 m³/s. OPEN AREA 40 %. STATIC ΔP 0 Pa. RACK LIMIT 0 kW. See the results table for the full readout. TILE FLOW0m³/sOPEN AREA40%STATIC ΔP0PaRACK LIMIT0kW Cold aisle0 m³/sIT rackRaised-floor plenum0 Pa2 installed · — requiredRack demand / delivered cooling0%No allowanceLimit 100%

Plenum pressure gives zero available flow. No finite tile count can meet the load.

Inputs

Tile and underfloor plenum
mm
mm
Pa
kg/m³
Air delivery to rack

The delivery fraction accounts for supply air that escapes the rack inlet.

kW
K
%

Calculation details

MeasureValue
Open area per tile0.1486 m²
Gross discharge per tile0 m³/s
Delivered airflow per tile0 m³/s
Delivered airflow across installed tiles0 m³/s
Airflow required at rack load0.552 m³/s
Minimum tiles per rack—
Maximum rack load at target ΔT0 kW
Rack load headroom-8 kW

Starting calculation

  1. The tile opening is 0.1486 m². Apply its discharge coefficient at 0 Pa to obtain 0 m³/s gross per tile.
  2. Usable airflow is zero, so a finite tile count cannot meet this rack load.

No finite number of tiles can serve the entered load at zero pressure. Restore airflow and measure the local pressure before sizing more tiles.

Calculation method

  • Aopen = width × depth × open fraction
  • Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
  • Supported rack kW = useful rack airflow × ρ × cp × ΔT

The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.

Engineering limits

Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.