68% grate for a 25 kW rack
A rack uses three high-flow grates with a good seal between supply and return paths.
Engineering schematic
Underfloor plenum & rack
Rack load headroom 34.8 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Open area per tile | 0.2527 m² |
| Gross discharge per tile | 1.256 m³/s |
| Delivered airflow per tile | 1.18 m³/s |
| Delivered airflow across installed tiles | 3.541 m³/s |
| Airflow required at rack load | 1.479 m³/s |
| Minimum tiles per rack | 2 tiles |
| Maximum rack load at target ΔT | 59.84 kW |
| Rack load headroom | 34.84 kW |
Update the highlighted inputs to see the results.
Starting calculation
- The tile opening is 0.2527 m². Apply its discharge coefficient at 33 Pa to obtain 1.256 m³/s gross per tile.
- After air delivery losses, one tile supplies 1.18 m³/s. Round the rack’s 1.479 m³/s requirement up to 2 tiles.
Large openings can change the plenum pressure itself. Rebalance and remeasure before relying on the constant-pressure estimate.
Calculation method
- Aopen = width × depth × open fraction
- Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
- Supported rack kW = useful rack airflow × ρ × cp × ΔT
The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.
Engineering limits
Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.
Related worked examples
DataCenterPUELab · Calculation sheet
68% grate for a 25 kW rack
Rack load headroom 34.8 kW
Inputs
- Open area
- 68% high-flow grate
- Tile width
- 609.6 mm
- Tile depth
- 609.6 mm
- Plenum static pressure
- 33 Pa
- Discharge coefficient
- 0.67
- Air density
- 1.2 kg/m³
- Rack IT load
- 25 kW
- Target rack ΔT
- 14 K
- Tiles serving this rack
- 3
- Air reaching the rack
- 94 %
Results
- Open area per tile
- 0.2527 m²
- Gross discharge per tile
- 1.256 m³/s
- Delivered airflow per tile
- 1.18 m³/s
- Delivered airflow across installed tiles
- 3.541 m³/s
- Airflow required at rack load
- 1.479 m³/s
- Minimum tiles per rack
- 2 tiles
- Maximum rack load at target ΔT
- 59.84 kW
- Rack load headroom
- 34.84 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.