Cool-climate waterside operation

A waterside plant uses a 16 °C supply setpoint and a 5 K total approach. The outdoor wet-bulb bins are illustrative.

Engineering schematic

Annual climate-bin dispatch

Live
Annual climate-bin dispatch FREE HOURS 4,500 h. ENERGY SAVE 1,342.7 MWh. COST SAVE 161k $. CO₂E AVOID 469.9 t CO₂e. See the results table for the full readout. FREE HOURS4,500hENERGY SAVE1,342.7MWhCOST SAVE161k$CO₂E AVOID469.9t CO₂e 1,300-3°1,4005°1,80010°1,70015°1,60021°96028°Full-freePartialMechanical°CEquivalent full-free cooling / year0%58% freeLimit 100%

5,067 h of equivalent full-free cooling per year.

Inputs

Operating limits
°C
°C
K
K
Load and utility rates
kWₜₕ
kW/kWₜₕ
kW/kWₜₕ
$/kWh
g/kWh
Annual climate bins

Enter six representative outdoor temperatures and annual hours. Any unentered hours, including lockouts, use mechanical cooling.

BinWet-bulbAnnual hours1
°C
h
2
°C
h
3
°C
h
4
°C
h
5
°C
h
6
°C
h

Calculation details

MeasureValue
Full-free outdoor cutoff11 °C
Mechanical cooling threshold17 °C
Full-free cooling hours4,500 h
Partial cooling hours1,700 h
Mechanical cooling hours2,560 h
Unentered hours assigned to mechanical0 h
Equivalent full-free cooling hours5,066.67 h
All-mechanical baseline energy2,847 MWh
Energy in full-free bins270 MWh
Energy in partial bins402.33 MWh
Energy in mechanical bins832 MWh
Modeled annual cooling energy1,504.33 MWh
Annual cooling energy savings1,342.67 MWh
Baseline cooling energy saved47.16 %
Annual energy cost savings161,120 $
Annual grid emissions avoided469.93 t CO₂e

Starting calculation

  1. Subtract 5 K of approach to get a 11 °C full-free cutoff. The entered bins give 4,500 full-free and 1,700 partial hours.
  2. Weight plant power by each bin. Annual cooling energy moves from 2,847 MWh to 1,504.33 MWh.

A warmer chilled-water supply raises the wet-bulb threshold for full free cooling. Confirm coil heat transfer can support that reset.

Calculation method

  • Full-free cutoff = applicable setpoint − total approach
  • Partial-free fraction = (full-free cutoff + band − bin temperature) ÷ band
  • Annual MWh = Σ(cooling kW × mode input ratio × hours) ÷ 1,000

Airside uses outdoor dry-bulb against the IT inlet setpoint. Waterside uses outdoor wet-bulb against chilled-water supply. Partial cooling linearly blends both plant intensities. Missing climate hours are assigned to mechanical cooling in an 8,760-hour year.

Engineering limits

ASHRAE A1/A2 recommended inlet temperature spans 18–27 °C. At reference elevation, dry-bulb allowable limits are 15–32 °C for A1 and 10–35 °C for A2. Apply equipment, humidity, contamination and elevation limits when screening outdoor hours. Include relevant fans and pumps in both plant intensities.