Hot-aisle recirculation penalty
A row with gaps between racks has 19% bypass and a 22% recirculation estimate.
Engineering schematic
Sensible air path
Sensible capacity headroom 14.1 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Rack and room sensible load | 41 kW |
| Air density at site elevation | 1.2 kg/m³ |
| Effective delivery fraction | 63.18 % |
| Rack air temperature rise | 10 K |
| Useful rack airflow | 3.396 m³/s |
| Required or measured supply airflow | 5.376 m³/s |
| Airflow delivery penalty | 1.979 m³/s |
| Total coil duty at entered SHR | 43.16 kWₜₕ |
| Rated sensible coil capacity | 55.1 kWₜₕ |
| Rated latent coil capacity | 2.9 kWₜₕ |
| Sensible capacity headroom | 14.1 kW |
Update the highlighted inputs to see the results.
Starting calculation
- Add IT and room heat for 41 kW sensible. The bypass and recirculation assumptions give 63.18% effective delivery.
- At 10 K and 1.2 kg/m³, the required fan supply is 5.376 m³/s (11,390 CFM).
Reduce recirculation in the model to approximate the airflow benefit of blanking panels and aisle separation.
Calculation method
- Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
- CFM ≈ 3.16 × W ÷ ΔT°F at reference density
- Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]
Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.
Engineering limits
The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.
Related worked examples
DataCenterPUELab · Calculation sheet
Hot-aisle recirculation penalty
Sensible capacity headroom 14.1 kW
Inputs
- IT heat load
- 38 kW
- Other sensible heat
- 3 kW
- Total coil capacity
- 58 kWₜₕ
- Sensible heat ratio
- 95 %
- Calculate
- Supply airflow
- Target rack ΔT
- 10 K
- Site elevation
- 0 m
- Supply air bypass
- 19 %
- Hot air recirculation
- 22 %
Results
- Rack and room sensible load
- 41 kW
- Air density at site elevation
- 1.2 kg/m³
- Effective delivery fraction
- 63.18 %
- Rack air temperature rise
- 10 K
- Useful rack airflow
- 3.396 m³/s
- Required or measured supply airflow
- 5.376 m³/s
- Airflow delivery penalty
- 1.979 m³/s
- Total coil duty at entered SHR
- 43.16 kWₜₕ
- Rated sensible coil capacity
- 55.1 kWₜₕ
- Rated latent coil capacity
- 2.9 kWₜₕ
- Sensible capacity headroom
- 14.1 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.