DataCenterPUELab

Hot-aisle recirculation penalty

A row with gaps between racks has 19% bypass and a 22% recirculation estimate.

Engineering schematic

Sensible air path

Live
Sensible air path SUPPLY FLOW 5.38 m³/s. RACK ΔT 10 K. SENSIBLE 41 kW. DENSITY 1.2 kg/m³. See the results table for the full readout. SUPPLY FLOW5.38m³/sRACK ΔT10KSENSIBLE41kWDENSITY1.2kg/m³ CRAC/CRAH95% SHRHot returnCold aisle3.4 m³/s10 Krack rise36.8% delivery lossSensible load / rated sensible capacity0%74% usedLimit 100%

Sensible capacity headroom 14.1 kW

Inputs

Rack and cooling unit
kW
kW
kWₜₕ
%
Air path

Bypass and recirculation reduce the fraction of supply air that delivers effective rack cooling.

K
m
%
%

Calculation details

MeasureValue
Rack and room sensible load41 kW
Air density at site elevation1.2 kg/m³
Effective delivery fraction63.18 %
Rack air temperature rise10 K
Useful rack airflow3.396 m³/s
Required or measured supply airflow5.376 m³/s
Airflow delivery penalty1.979 m³/s
Total coil duty at entered SHR43.16 kWₜₕ
Rated sensible coil capacity55.1 kWₜₕ
Rated latent coil capacity2.9 kWₜₕ
Sensible capacity headroom14.1 kW

Starting calculation

  1. Add IT and room heat for 41 kW sensible. The bypass and recirculation assumptions give 63.18% effective delivery.
  2. At 10 K and 1.2 kg/m³, the required fan supply is 5.376 m³/s (11,390 CFM).

Reduce recirculation in the model to approximate the airflow benefit of blanking panels and aisle separation.

Calculation method

  • Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
  • CFM ≈ 3.16 × W ÷ ΔT°F at reference density
  • Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]

Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.

Engineering limits

The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.