Rack rise from measured supply flow
Commissioning reports 2.25 m³/s of supply volume for a 31 kW sensible load. Solve for the estimated temperature rise.
Engineering schematic
Sensible air path
Sensible capacity headroom 11.8 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Rack and room sensible load | 31 kW |
| Air density at site elevation | 1.2 kg/m³ |
| Effective delivery fraction | 88.32 % |
| Rack air temperature rise | 12.92 K |
| Useful rack airflow | 1.987 m³/s |
| Required or measured supply airflow | 2.25 m³/s |
| Airflow delivery penalty | 0.263 m³/s |
| Total coil duty at entered SHR | 32.63 kWₜₕ |
| Rated sensible coil capacity | 42.75 kWₜₕ |
| Rated latent coil capacity | 2.25 kWₜₕ |
| Sensible capacity headroom | 11.75 kW |
Update the highlighted inputs to see the results.
Starting calculation
- Add IT and room heat for 31 kW sensible. The bypass and recirculation assumptions give 88.32% effective delivery.
- At 2.25 m³/s supply and 1.2 kg/m³, the heat balance gives 12.92 K of rack temperature rise.
Compare the modeled rise with measured inlet and exhaust temperatures. A disagreement may point to air bypass or sensor placement.
Calculation method
- Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
- CFM ≈ 3.16 × W ÷ ΔT°F at reference density
- Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]
Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.
Engineering limits
The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.
Related worked examples
DataCenterPUELab · Calculation sheet
Rack rise from measured supply flow
Sensible capacity headroom 11.8 kW
Inputs
- IT heat load
- 29 kW
- Other sensible heat
- 2 kW
- Total coil capacity
- 45 kWₜₕ
- Sensible heat ratio
- 95 %
- Calculate
- Rack temperature rise
- Measured supply flow
- 2.25 m³/s
- Site elevation
- 0 m
- Supply air bypass
- 8 %
- Hot air recirculation
- 4 %
Results
- Rack and room sensible load
- 31 kW
- Air density at site elevation
- 1.2 kg/m³
- Effective delivery fraction
- 88.32 %
- Rack air temperature rise
- 12.92 K
- Useful rack airflow
- 1.987 m³/s
- Required or measured supply airflow
- 2.25 m³/s
- Airflow delivery penalty
- 0.263 m³/s
- Total coil duty at entered SHR
- 32.63 kWₜₕ
- Rated sensible coil capacity
- 42.75 kWₜₕ
- Rated latent coil capacity
- 2.25 kWₜₕ
- Sensible capacity headroom
- 11.75 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.