No positive plenum pressure
A stopped supply fan leaves zero measured pressure across the perforated tile.
Engineering schematic
Underfloor plenum & rack
Plenum pressure gives zero available flow. No finite tile count can meet the load.
Inputs
Calculation details
| Measure | Value |
|---|---|
| Open area per tile | 0.1486 m² |
| Gross discharge per tile | 0 m³/s |
| Delivered airflow per tile | 0 m³/s |
| Delivered airflow across installed tiles | 0 m³/s |
| Airflow required at rack load | 0.552 m³/s |
| Minimum tiles per rack | — |
| Maximum rack load at target ΔT | 0 kW |
| Rack load headroom | -8 kW |
Update the highlighted inputs to see the results.
Starting calculation
- The tile opening is 0.1486 m². Apply its discharge coefficient at 0 Pa to obtain 0 m³/s gross per tile.
- Usable airflow is zero, so a finite tile count cannot meet this rack load.
No finite number of tiles can serve the entered load at zero pressure. Restore airflow and measure the local pressure before sizing more tiles.
Calculation method
- Aopen = width × depth × open fraction
- Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
- Supported rack kW = useful rack airflow × ρ × cp × ΔT
The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.
Engineering limits
Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.
Related worked examples
DataCenterPUELab · Calculation sheet
No positive plenum pressure
Plenum pressure gives zero available flow. No finite tile count can meet the load.
Inputs
- Open area
- 40% perforated
- Tile width
- 609.6 mm
- Tile depth
- 609.6 mm
- Plenum static pressure
- 0 Pa
- Discharge coefficient
- 0.62
- Air density
- 1.2 kg/m³
- Rack IT load
- 8 kW
- Target rack ΔT
- 12 K
- Tiles serving this rack
- 2
- Air reaching the rack
- 85 %
Results
- Open area per tile
- 0.1486 m²
- Gross discharge per tile
- 0 m³/s
- Delivered airflow per tile
- 0 m³/s
- Delivered airflow across installed tiles
- 0 m³/s
- Airflow required at rack load
- 0.552 m³/s
- Minimum tiles per rack
- —
- Maximum rack load at target ΔT
- 0 kW
- Rack load headroom
- -8 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.