Air duty after liquid heat capture
A liquid-assisted row rejects 17 kW into the room. Add the room sensible load to size the remaining air supply.
Engineering schematic
Sensible air path
Sensible capacity headroom 6.5 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Rack and room sensible load | 19 kW |
| Air density at site elevation | 1.2 kg/m³ |
| Effective delivery fraction | 91.18 % |
| Rack air temperature rise | 15 K |
| Useful rack airflow | 1.049 m³/s |
| Required or measured supply airflow | 1.151 m³/s |
| Airflow delivery penalty | 0.101 m³/s |
| Total coil duty at entered SHR | 19.39 kWₜₕ |
| Rated sensible coil capacity | 25.48 kWₜₕ |
| Rated latent coil capacity | 0.52 kWₜₕ |
| Sensible capacity headroom | 6.48 kW |
Update the highlighted inputs to see the results.
Starting calculation
- Add IT and room heat for 19 kW sensible. The bypass and recirculation assumptions give 91.18% effective delivery.
- At 15 K and 1.2 kg/m³, the required fan supply is 1.151 m³/s (2,438 CFM).
Enter the residual load from the CDU calculator as IT heat rejected to air.
Calculation method
- Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
- CFM ≈ 3.16 × W ÷ ΔT°F at reference density
- Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]
Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.
Engineering limits
The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.
Related worked examples
DataCenterPUELab · Calculation sheet
Air duty after liquid heat capture
Sensible capacity headroom 6.5 kW
Inputs
- IT heat load
- 17 kW
- Other sensible heat
- 2 kW
- Total coil capacity
- 26 kWₜₕ
- Sensible heat ratio
- 98 %
- Calculate
- Supply airflow
- Target rack ΔT
- 15 K
- Site elevation
- 0 m
- Supply air bypass
- 6 %
- Hot air recirculation
- 3 %
Results
- Rack and room sensible load
- 19 kW
- Air density at site elevation
- 1.2 kg/m³
- Effective delivery fraction
- 91.18 %
- Rack air temperature rise
- 15 K
- Useful rack airflow
- 1.049 m³/s
- Required or measured supply airflow
- 1.151 m³/s
- Airflow delivery penalty
- 0.101 m³/s
- Total coil duty at entered SHR
- 19.39 kWₜₕ
- Rated sensible coil capacity
- 25.48 kWₜₕ
- Rated latent coil capacity
- 0.52 kWₜₕ
- Sensible capacity headroom
- 6.48 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.