Sea-level contained cold aisle

A contained aisle serves a 24 kW rack load with little bypass or recirculation at sea level.

Engineering schematic

Sensible air path

Live
Sensible air path SUPPLY FLOW 1.71 m³/s. RACK ΔT 13 K. SENSIBLE 25.5 kW. DENSITY 1.2 kg/m³. See the results table for the full readout. SUPPLY FLOW1.71m³/sRACK ΔT13KSENSIBLE25.5kWDENSITY1.2kg/m³ CRAC/CRAH96% SHRHot returnCold aisle1.62 m³/s13 Krack rise4.9% delivery lossSensible load / rated sensible capacity0%76% usedLimit 100%

Sensible capacity headroom 8.1 kW

Inputs

Rack and cooling unit
kW
kW
kWₜₕ
%
Air path

Bypass and recirculation reduce the fraction of supply air that delivers effective rack cooling.

K
m
%
%

Calculation details

MeasureValue
Rack and room sensible load25.5 kW
Air density at site elevation1.2 kg/m³
Effective delivery fraction95.06 %
Rack air temperature rise13 K
Useful rack airflow1.625 m³/s
Required or measured supply airflow1.709 m³/s
Airflow delivery penalty0.084 m³/s
Total coil duty at entered SHR26.56 kWₜₕ
Rated sensible coil capacity33.6 kWₜₕ
Rated latent coil capacity1.4 kWₜₕ
Sensible capacity headroom8.1 kW

Starting calculation

  1. Add IT and room heat for 25.5 kW sensible. The bypass and recirculation assumptions give 95.06% effective delivery.
  2. At 13 K and 1.2 kg/m³, the required fan supply is 1.709 m³/s (3,622 CFM).

Compare the fan supply requirement with useful rack flow. Containment narrows the gap between them.

Calculation method

  • Q (m³/s) = sensible kW ÷ (ρ × 1.006 × ΔT)
  • CFM ≈ 3.16 × W ÷ ΔT°F at reference density
  • Supply airflow = useful airflow ÷ [(1 − bypass) × (1 − recirculation)]

Use sea-level reference density of 1.20 kg/m³, adjusted by standard atmospheric pressure ratio at the entered elevation, with fixed specific heat. Rated sensible coil capacity is nameplate total capacity times SHR.

Engineering limits

The recirculation factor is a delivery estimate. Use measured inlet and return conditions, fan curves and site air balancing for equipment selection. A very high calculated ΔT calls for review of the assumed load and airflow.