DataCenterPUELab

Warm wet-bulb climate with limited savings

A warm climate has most hours above the full-free threshold. Apply a narrow partial-cooling band.

Engineering schematic

Annual climate-bin dispatch

Live
Annual climate-bin dispatch FREE HOURS 180 h. ENERGY SAVE 101.8 MWh. COST SAVE 12k $. CO₂E AVOID 35.6 t CO₂e. See the results table for the full readout. FREE HOURS180hENERGY SAVE101.8MWhCOST SAVE12k$CO₂E AVOID35.6t CO₂e 1806°34010°85013°1,80018°2,40023°3,19028°Full-freePartialMechanical°CEquivalent full-free cooling / year0%4% freeLimit 100%

384 h of equivalent full-free cooling per year.

Inputs

Operating limits
°C
°C
K
K
Load and utility rates
kWₜₕ
kW/kWₜₕ
kW/kWₜₕ
$/kWh
g/kWh
Annual climate bins

Enter six representative outdoor temperatures and annual hours. Any unentered hours, including lockouts, use mechanical cooling.

BinWet-bulbAnnual hours1
°C
h
2
°C
h
3
°C
h
4
°C
h
5
°C
h
6
°C
h

Calculation details

MeasureValue
Full-free outdoor cutoff8 °C
Mechanical cooling threshold13 °C
Full-free cooling hours180 h
Partial cooling hours340 h
Mechanical cooling hours8,240 h
Unentered hours assigned to mechanical0 h
Equivalent full-free cooling hours384 h
All-mechanical baseline energy2,847 MWh
Energy in full-free bins10.8 MWh
Energy in partial bins56.44 MWh
Energy in mechanical bins2,678 MWh
Modeled annual cooling energy2,745.24 MWh
Annual cooling energy savings101.76 MWh
Baseline cooling energy saved3.57 %
Annual energy cost savings12,211 $
Annual grid emissions avoided35.62 t CO₂e

Starting calculation

  1. Subtract 5 K of approach to get a 8 °C full-free cutoff. The entered bins give 180 full-free and 340 partial hours.
  2. Weight plant power by each bin. Annual cooling energy moves from 2,847 MWh to 2,745.24 MWh.

Check equivalent full-free hours as well as mode hours. A partial-cooling hour displaces a fraction of the chiller duty.

Calculation method

  • Full-free cutoff = applicable setpoint − total approach
  • Partial-free fraction = (full-free cutoff + band − bin temperature) ÷ band
  • Annual MWh = Σ(cooling kW × mode input ratio × hours) ÷ 1,000

Airside uses outdoor dry-bulb against the IT inlet setpoint. Waterside uses outdoor wet-bulb against chilled-water supply. Partial cooling linearly blends both plant intensities. Missing climate hours are assigned to mechanical cooling in an 8,760-hour year.

Engineering limits

ASHRAE A1/A2 recommended inlet temperature spans 18–27 °C. At reference elevation, dry-bulb allowable limits are 15–32 °C for A1 and 10–35 °C for A2. Apply equipment, humidity, contamination and elevation limits when screening outdoor hours. Include relevant fans and pumps in both plant intensities.