Raised-floor perforated tile airflow calculator

Estimate CFM per floor tile, tile count and supported rack kW from open area and plenum static pressure.

Engineering schematic

Underfloor plenum & rack

Live
Underfloor plenum & rack TILE FLOW 0.45 m³/s. OPEN AREA 40 %. STATIC ΔP 20 Pa. RACK LIMIT 19.7 kW. See the results table for the full readout. TILE FLOW0.45m³/sOPEN AREA40%STATIC ΔP20PaRACK LIMIT19.7kW Cold aisle0.45 m³/sIT rackRaised-floor plenum20 Pa3 installed · 2 requiredRack demand / delivered cooling0%61% usedLimit 100%

Rack load headroom 7.7 kW

Inputs

Tile and underfloor plenum
mm
mm
Pa
kg/m³
Air delivery to rack

The delivery fraction accounts for supply air that escapes the rack inlet.

kW
K
%

Calculation details

MeasureValue
Open area per tile0.1486 m²
Gross discharge per tile0.532 m³/s
Delivered airflow per tile0.452 m³/s
Delivered airflow across installed tiles1.357 m³/s
Airflow required at rack load0.828 m³/s
Minimum tiles per rack2 tiles
Maximum rack load at target ΔT19.66 kW
Rack load headroom7.66 kW

Calculation method

  • Aopen = width × depth × open fraction
  • Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
  • Supported rack kW = useful rack airflow × ρ × cp × ΔT

The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.

Engineering limits

Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.

Worked examples