Three-phase rack PDU load balance calculator

Check A/B whip phase currents, Wye neutral load and failover headroom on 415/240 V or 208/120 V service.

Engineering schematic

Wye A/B rack distribution

Live
Wye A/B rack distribution LIMIT / LEG 25.6 A. WORST LEG 23.7 A. NEUTRAL MAX 3.6 A. HEADROOM 1.9 A. See the results table for the full readout. LIMIT / LEG25.6AWORST LEG23.7ANEUTRAL MAX3.6AHEADROOM1.9A A whipN 1.9 AB whipN 2 A415/240 V WyeWorst survivorL123.7 AL220.6 AL319.7 ATick = breaker limitWorst surviving phase / continuous limit0%93% usedLimit 100%

Failover breaker headroom 1.9 A

Inputs

Breaker and supply

Enter the share on each phase that has a single cord and no independent transfer path.

A
%
A whip · normal load
kW
kW
kW
B whip · normal load
kW
kW
kW

Calculation details

MeasureValue
Total normal rack load14.6 kW
80% continuous limit per phase25.6 A
Highest phase current after failover23.68 A
Minimum continuous-breaker headroom1.92 A
Highest fundamental neutral current3.59 A
Balanced real-power limit per whip17.51 kW
A normal · L111.4 A
A normal · L210.53 A
A normal · L39.21 A
B normal · L112.28 A
B normal · L210.09 A
B normal · L310.53 A
A surviving · L123.68 A
A surviving · L220.61 A
A surviving · L319.74 A
B surviving · L123.68 A
B surviving · L220.61 A
B surviving · L319.74 A
A normal · neutral1.91 A
B normal · neutral2.01 A
A surviving · neutral3.59 A
B surviving · neutral3.59 A
A normal · phase imbalance11.27 %
B normal · phase imbalance12 %
A surviving · phase imbalance10.96 %
B surviving · phase imbalance10.96 %
Rack load shed on loss of A0 kW
Rack load shed on loss of B0 kW

Calculation method

  • Iphase = 1,000 × kWphase ÷ (VLN × PF)
  • Ineutral = √(Ia² + Ib² + Ic² − IaIb − IbIc − IcIa)
  • Continuous current limit = 0.80 × breaker rating

Use nominal line-to-neutral voltage and phase-to-neutral real kW. Imbalance is largest deviation from the phase mean divided by that mean. Transferable loads from the failed whip are added to corresponding phases on the survivor. Non-transferable single-cord loads on the failed whip drop.

Engineering limits

The neutral model uses fundamental currents with a common power factor and 120° phase spacing. Check harmonic neutral current, conductor ampacity, breaker listing and local code separately. The screen uses 80% of a standard-rated breaker for a continuous load of three hours or more.