NFPA 20 · Worked example
Electric 1,000 GPM pump reference
A test gives 123 psi at churn, 100 psi at rated flow and 72 psi at 150% flow. The pump curve lists a 102 BHP peak.
Inputs
Three-point fire pump curve
Edit inputsThe three points and entered suction margin meet the screening criteria.
How to read this example
The peak can exceed the two calculated shaft loads. Compare the full-curve mechanical requirement before selecting the motor.
Open the base calculatorCalculated values
- Churn · percent of rated pressure
- 123 %
- 150% flow · percent of rated pressure
- 72 %
- 150% test flow
- 1,500 GPM
- Reserve below 140% ceiling
- 17 pp
- Reserve above 65% floor
- 7 pp
- Flowing suction reserve
- 20 psi
- Rated water power
- 58.34 hp
- 150% water power
- 63.01 hp
- Rated shaft load
- 81.03 hp
- 150% shaft load
- 94.05 hp
- Electric mechanical power estimate
- 102 hp
- Diesel pre-derating power estimate
- 113.33 hp
- Pressure maintenance flow estimate
- 1.8 GPM
- Jockey discharge target
- 161 psi
Equations and assumptions
Churn ≤ 140% of rated net pressureP_150 ≥ 65% of rated net pressureWater hp = Q ΔP / 1714BHP = water hp / pump efficiency
Enter net pump pressures at churn, rated flow and 150% flow. Use the listed full-curve peak BHP and the manufacturer’s site derating and driver data for selection.
The suction field screens a measured gauge pressure against the entered minimum. Confirm the adopted standard, the supply type, its available flow, intake arrangement and pump suction limits.
The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.