Methodology
Calculation basis, units, screening assumptions and source references for the fire protection worksheets.
Use the worksheet at a defined point
Choose a sprinkler, pipe segment, water-supply test, pump, dry system, tank, standpipe or enclosure. Enter the measured or listed values and confirm their elevation datum, units and design basis.
Each worksheet gives preliminary arithmetic and screening checkpoints. Confirm the adopted edition, listings and Authority Having Jurisdiction requirements before using results in a design.
Unit and export conventions
Water flows use US gallons per minute and convert to litres per minute. Gauge pressures use psi or bar. Agent enclosure pressure uses psf or pascals. K-factors switch with both flow and the square root of pressure.
Switching units keeps the physical inputs. The worksheet shows rounded values and exports the full numerical results in the selected units. SVG and PNG capture the live diagram. The print view fits a single A4 page.
Review the application limits
- Sprinkler K-factor
The pressure is the residual at this sprinkler. Evaluate the remote design area, coverage limits, other operating sprinklers and water supply in the system calculation.
- Sprinkler pipe friction
Velocity is screened against an editable project criterion. The calculation uses one pipe segment at a steady flow.
- Hydrant flow test
Extrapolation is sensitive to small pressure drops, nearby demands and test conditions. Correct elevation and supply losses before comparing a building demand.
- Fire pump curve
The jockey estimate uses at least 1 GPM or the entered leakage rate and aims for churn net pressure plus static suction. Compare with one sprinkler flow for aboveground-only pressure maintenance.
- Dry-pipe air volume
The 30-minute curve describes air restoration. Water delivery after sprinkler operation is evaluated separately.
- Fire water storage
The estimate assumes constant demand and no makeup flow. Confirm net capacity, tank configuration and suction details with the tank and pump suppliers.
- Standpipe pressure zoning
Residual and static inputs describe separate conditions. Reconcile a static pressure below the required flowing base or any modeled negative static before selecting a zone.
- Clean-agent flooding
The vent estimate is a quasi-steady positive-pressure air-orifice calculation. It uses the entered peak factor and assumes an open vent. The model screens peak pressures up to 5% of ambient pressure. It omits negative transients, vent opening pressure, humidity and manufacturer-specific discharge profiles.
Sources and adoption
Worksheet references include NFPA development records, official guidance, corrections and manufacturer manuals. The adopted standard and amendments control project criteria.